This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term "doorset" will be used to cover both doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples:
-   integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classification,
-   glazed elements including vision panels and framed glazed doorsets,
-   air transfer grilles (louvres and/or vents),
-   side, transom or over panels,
-   items of building hardware,
-   decorative and protective finishes,
-   intumescent seals and non-intumescent (smoke, draught or acoustic) seals,
-   alternative supporting construction(s).
This document does not cover horizontal doorsets.
The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

  • Standard
    214 pages
    English language
    e-Library read for
    ×1 day

This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term "doorset" will be used to cover both doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples:
-   integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classification,
-   glazed elements including vision panels and framed glazed doorsets,
-   air transfer grilles (louvres and/or vents),
-   side, transom or over panels,
-   items of building hardware,
-   decorative and protective finishes,
-   intumescent seals and non-intumescent (smoke, draught or acoustic) seals,
-   alternative supporting construction(s).
This document does not cover horizontal doorsets.
The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

  • Standard
    214 pages
    English language
    e-Library read for
    ×1 day

This document establishes the general principles for the conditioning procedures for test specimens tested according to the European standards for reaction to fire.
The rules for the selection of substrates for construction products when carrying out reaction to fire tests are also detailed in this document. In order to use the extension rules set in this document, no modification of the standard substrate is allowed.
This document does not contain requirements for:
—   the pre-drying of test specimens for the non-combustibility test according to EN ISO 1182;
—   methods of cleaning (e.g. washing) and other methods for the assessment of durability aspects, which are dealt with in the relevant product standards.

  • Standard
    12 pages
    English language
    e-Library read for
    ×1 day

This document defines rules for extended applications, provides guidance, and, where appropriate, specifies procedures, for variations of certain parameters and factors associated with the design of internal non-loadbearing ceilings constructed of metal faced sandwich panels that have been tested in accordance with EN 1364 2, which could generate a classification in accordance with EN 13501 2.
This document applies to double skin metal faced sandwich panels which have an insulating core bonded to both facings as defined in EN 14509, not stabilizing a whole building or parts of it.

  • Standard
    24 pages
    English language
    e-Library read for
    ×1 day

This document specifies a method for determining the fire resistance of air transfer grilles (ATG).
It is applicable to air transfer grilles intended for installation in building components (typically walls, floors or ceilings). The orientation of the installation of the air transfer grille can be vertical or horizontal.
The closing mechanism of the air transfer grille can come from expansion of material and/or from any mechanical or electrical closing device.
This document is applicable to fire resistant or fire resistant and smoke control air transfer grilles.
An additional test configuration is valid for fire resistant or fire resistant and smoke control air transfer grilles in applications where flame impingement is a risk during open state from start of fire (see Annex A).
This document evaluates the behaviour of the air transfer grille when exposed to the heating curve described in EN 1363 1 and the standard pressure described in EN 1363 1. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes under fire conditions. Such phenomena are only noted in describing the general behaviour of test specimens during the test.
The determination of the rate of leakage of smoke at ambient temperature or at 200 °C as an optional requirement for ATG with declared smoke control is specified in EN 1634 3.
This document is not applicable to the determination of the fire resistance of air transfer grilles that are used in ducts because ATG are considered as separating elements. The test method for ATG used in ducts is described in the corresponding duct standards.
This document is not applicable to the determination of the fire resistance of a fire damper or a fire barrier connected to a duct one or both sides, as an ATG is tested as a fire-separating element on its own. Fire dampers are tested according to EN 1366 2. Non-mechanical fire barriers are tested according to EN 1366 12.
This document is not applicable to the determination of the fire resistance of air transfer grilles in fire doors, shutters and openable windows as specified in EN 1634 1 and EN 1364 2, because the deformation of fire doors, shutters and openable windows in fire conditions differs from the deformation of flexible/rigid walls. Moreover, the location of thermocouples in the door standard is too specific to be handled in this document.
All values given in this document are nominal unless otherwise specified.

  • Standard
    28 pages
    English language
    e-Library read for
    ×1 day

This document defines rules for extended applications, provides guidance, and, where appropriate, defines procedures, for variations of certain parameters and factors associated with the design of internal and external non-loadbearing walls constructed of metal sandwich panels and that have been tested in accordance with EN 1364 1, which could generate a classification in accordance with EN 13501 2.
This document applies for double skin metal faced sandwich panels having an insulating core bonded to both facings as defined in EN 14509 not stabilizing a whole building or parts of it.

  • Standard
    26 pages
    English language
    e-Library read for
    ×1 day

This document establishes the general principles for the conditioning procedures for test specimens tested according to the European standards for reaction to fire.
The rules for the selection of substrates for construction products when carrying out reaction to fire tests are also detailed in this document. In order to use the extension rules set in this document, no modification of the standard substrate is allowed.
This document does not contain requirements for:
—   the pre-drying of test specimens for the non-combustibility test according to EN ISO 1182;
—   methods of cleaning (e.g. washing) and other methods for the assessment of durability aspects, which are dealt with in the relevant product standards.

  • Standard
    12 pages
    English language
    e-Library read for
    ×1 day

This document defines rules for extended applications, provides guidance, and, where appropriate, specifies procedures, for variations of certain parameters and factors associated with the design of internal non-loadbearing ceilings constructed of metal faced sandwich panels that have been tested in accordance with EN 1364 2, which could generate a classification in accordance with EN 13501 2.
This document applies to double skin metal faced sandwich panels which have an insulating core bonded to both facings as defined in EN 14509, not stabilizing a whole building or parts of it.

  • Standard
    24 pages
    English language
    e-Library read for
    ×1 day

This document defines rules for extended applications, provides guidance, and, where appropriate, defines procedures, for variations of certain parameters and factors associated with the design of internal and external non-loadbearing walls constructed of metal sandwich panels and that have been tested in accordance with EN 1364 1, which could generate a classification in accordance with EN 13501 2.
This document applies for double skin metal faced sandwich panels having an insulating core bonded to both facings as defined in EN 14509 not stabilizing a whole building or parts of it.

  • Standard
    26 pages
    English language
    e-Library read for
    ×1 day

This document specifies a method for determining the fire resistance of air transfer grilles (ATG).
It is applicable to air transfer grilles intended for installation in building components (typically walls, floors or ceilings). The orientation of the installation of the air transfer grille can be vertical or horizontal.
The closing mechanism of the air transfer grille can come from expansion of material and/or from any mechanical or electrical closing device.
This document is applicable to fire resistant or fire resistant and smoke control air transfer grilles.
An additional test configuration is valid for fire resistant or fire resistant and smoke control air transfer grilles in applications where flame impingement is a risk during open state from start of fire (see Annex A).
This document evaluates the behaviour of the air transfer grille when exposed to the heating curve described in EN 1363 1 and the standard pressure described in EN 1363 1. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes under fire conditions. Such phenomena are only noted in describing the general behaviour of test specimens during the test.
The determination of the rate of leakage of smoke at ambient temperature or at 200 °C as an optional requirement for ATG with declared smoke control is specified in EN 1634 3.
This document is not applicable to the determination of the fire resistance of air transfer grilles that are used in ducts because ATG are considered as separating elements. The test method for ATG used in ducts is described in the corresponding duct standards.
This document is not applicable to the determination of the fire resistance of a fire damper or a fire barrier connected to a duct one or both sides, as an ATG is tested as a fire-separating element on its own. Fire dampers are tested according to EN 1366 2. Non-mechanical fire barriers are tested according to EN 1366 12.
This document is not applicable to the determination of the fire resistance of air transfer grilles in fire doors, shutters and openable windows as specified in EN 1634 1 and EN 1364 2, because the deformation of fire doors, shutters and openable windows in fire conditions differs from the deformation of flexible/rigid walls. Moreover, the location of thermocouples in the door standard is too specific to be handled in this document.
All values given in this document are nominal unless otherwise specified.

  • Standard
    28 pages
    English language
    e-Library read for
    ×1 day

This document specifies the heating condition, method of test and criteria for the evaluation of the ability of a penetration sealing system to maintain the integrity and insulation of a fire-separating element at the position at which it has been penetrated. This document assesses: the effect of such penetrations on the integrity and insulation performance of the element concerned, the integrity and insulation performance of the penetration sealing system, and the insulation performance of the penetrating service or services, and where appropriate, the integrity failure of a service. NOTE 1 Optional water and air leakage tests are included in Annex A. NOTE 2 Explanatory notes are included in Annex B.

  • Standard
    27 pages
    English language
    sale 15% off

This document describes methods for simulating the mechanical loads that can be imparted to passive fire protection (PFP) materials and systems by explosions resulting from releases of flammable gas, pressurized liquefied gas, flashing liquid fuels, or dust that can precede a fire. These methods can be used to determine the resistance of passive fire protection materials to such events. This document considers PFP materials applied to substrates that are subject to the combined effects of pressure and drag that occur in the flow path of an explosion. This document excludes specimens in which the substrate is subject to plastic deformation or brittle failure.

  • Standard
    17 pages
    English language
    sale 15% off

This document describes installation scenarios and available test methods and national legislations to be considered when determining the external fire performance of roof systems, when combined with BAPV.

  • Technical report
    14 pages
    English language
    e-Library read for
    ×1 day

This document describes a test that determines the rate of leakage of ambient (cold) and medium (warm) temperature smoke from one side of door and shutter assemblies to the other under the specified test conditions. This test method is applicable to door and shutter assemblies and self-closing operable glazed elements of different configurations intended for the purpose of controlling the passage of smoke in case of fire. Wherever door and shutter assemblies are referred to in this document, it also applies to self-closing glazed elements. The fire resistance of glazed elements is determined by tests in accordance with ISO 3009.
The acceptable leakage rates for different situations are not addressed in this document, but rather are specified by the regulations of the controlling authorities.

  • Standard
    28 pages
    English language
    e-Library read for
    ×1 day
  • Standard
    23 pages
    English language
    sale 15% off
  • Standard
    2 pages
    English language
    sale 15% off
  • Standard
    2 pages
    French language
    sale 15% off
  • Amendment
    5 pages
    English language
    e-Library read for
    ×1 day

This document describes the test and assessment procedure for determining the contribution of reactive fire protection systems to the fire resistance of solid steel bars used as tension members, when exposed to the standard temperature/time curve specified in EN 1363-1. In special circumstances, where specified in National Building Regulations, there can be a need to subject reactive fire protection systems to a slow heating curve (smouldering fire) as defined in EN 1363-2. The corresponding test and assessment procedure are described in Annex E. The fire protection performance is determined by testing mechanically loaded steel bars in horizontal orientation. Information regarding the testing of additional unloaded specimens is given to assess the influence of the bar orientation and smouldering fire behaviour.
The principles of the testing and assessment procedure can also be applied for other section shapes such as angles, channels and flats. This document does not include steel bars used as reinforcement in concrete construction.
The document is applicable to steel bars up to a maximum diameter of 130 mm. In the case of rectangular bars, the maximum edge length shall be limited to 130 mm with a maximum aspect ratio of 2:1 against the shorter edge length.
The test programme and the assessment are designed to cover:
-   a range of valid fire protection classification periods;
-   a range of thickness of the applied reactive fire protection system;
-   a range of steel bar dimensions and profiles;
-   a range of specified design temperatures;
-   a range of load utilisation factors in case of fire;
-   a range of bar orientation.
This document also provides the assessment procedure, which prescribes how the analysis of the test data shall be made and gives guidance on the procedures by which interpolation shall be undertaken. The assessment procedure is used to establish:
a)   on the basis of data derived from mechanically loaded testing steel bar, any practical constraints on the use of the reactive fire protection system under fire test conditions (the physical performance);
b)   on the basis of the temperature data derived from testing steel bar the thermal properties of the reactive fire protection system (the thermal performance).
The limits of applicability of the results of the assessment arising from the fire test are defined together with permitted direct application of the results to different steel types and sizes over the range of thicknesses of the applied reactive fire protection system tested.

  • Standard
    71 pages
    English language
    e-Library read for
    ×1 day

This document describes the test and assessment procedure for determining the contribution of reactive fire protection systems to the fire resistance of solid steel bars used as tension members, when exposed to the standard temperature/time curve specified in EN 1363-1. In special circumstances, where specified in National Building Regulations, there can be a need to subject reactive fire protection systems to a slow heating curve (smouldering fire) as defined in EN 1363-2. The corresponding test and assessment procedure are described in Annex E. The fire protection performance is determined by testing mechanically loaded steel bars in horizontal orientation. Information regarding the testing of additional unloaded specimens is given to assess the influence of the bar orientation and smouldering fire behaviour.
The principles of the testing and assessment procedure can also be applied for other section shapes such as angles, channels and flats. This document does not include steel bars used as reinforcement in concrete construction.
The document is applicable to steel bars up to a maximum diameter of 130 mm. In the case of rectangular bars, the maximum edge length shall be limited to 130 mm with a maximum aspect ratio of 2:1 against the shorter edge length.
The test programme and the assessment are designed to cover:
-   a range of valid fire protection classification periods;
-   a range of thickness of the applied reactive fire protection system;
-   a range of steel bar dimensions and profiles;
-   a range of specified design temperatures;
-   a range of load utilisation factors in case of fire;
-   a range of bar orientation.
This document also provides the assessment procedure, which prescribes how the analysis of the test data shall be made and gives guidance on the procedures by which interpolation shall be undertaken. The assessment procedure is used to establish:
a)   on the basis of data derived from mechanically loaded testing steel bar, any practical constraints on the use of the reactive fire protection system under fire test conditions (the physical performance);
b)   on the basis of the temperature data derived from testing steel bar the thermal properties of the reactive fire protection system (the thermal performance).
The limits of applicability of the results of the assessment arising from the fire test are defined together with permitted direct application of the results to different steel types and sizes over the range of thicknesses of the applied reactive fire protection system tested.

  • Standard
    71 pages
    English language
    e-Library read for
    ×1 day

This document describes methods for simulating the mechanical loads that can be imparted to passive fire protection (PFP) materials and systems by explosions resulting from releases of flammable gas, pressurized liquefied gas, flashing liquid fuels, or dust that can precede a fire. These methods can be used to determine the resistance of passive fire protection materials to such events. This document considers PFP materials applied to panels, plates, etc. that can be used as divisional elements. The loading on this type of element predominantly results from explosion overpressure applied and drag loadings are typically minimal.

  • Standard
    14 pages
    English language
    sale 15% off

(1) EN 1994-1-2 gives rules for the design of steel-concrete composite structures for the accidental design situation of fire exposure. It only identifies differences from, or supplements to, rules for normal temperature design.
(2) EN 1994-1-2 only applies to structures, or parts of structures, that are within the scope of EN1994-1-1 and are designed accordingly.

  • Draft
    136 pages
    English language
    e-Library read for
    ×1 day

This document specifies a method of test for determining the ignitability of products by direct small flame impingement under zero impressed irradiance using vertically oriented test specimens.

  • Standard
    35 pages
    English language
    e-Library read for
    ×1 day

This document specifies a method of test for determining the ignitability of products by direct small flame impingement under zero impressed irradiance using vertically oriented test specimens.

  • Standard
    35 pages
    English language
    e-Library read for
    ×1 day

This document specifies a method of test for determining the ignitability of products by direct small flame impingement under zero impressed irradiance using vertically oriented test specimens.

  • Standard
    27 pages
    English language
    sale 15% off
  • Standard
    28 pages
    French language
    sale 15% off

This document describes a test that determines the rate of leakage of ambient (cold) and medium (warm) temperature smoke from one side of door and shutter assemblies to the other under the specified test conditions. This test method is applicable to door and shutter assemblies and self-closing operable glazed elements of different configurations intended for the purpose of controlling the passage of smoke in case of fire. Wherever door and shutter assemblies are referred to in this document, it also applies to self-closing glazed elements. The fire resistance of glazed elements is determined by tests in accordance with ISO 3009. The acceptable leakage rates for different situations are not addressed in this document, but rather are specified by the regulations of the controlling authorities.

  • Standard
    28 pages
    English language
    e-Library read for
    ×1 day
  • Standard
    23 pages
    English language
    sale 15% off

This document is applicable to hinged and pivoted doors, doorsets and door assemblies with glass based leaves. Throughout this document the term “doorset” will be used to cover doors, doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1 and/or EN 1634-3 and/or EN 1191.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
—   integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
—   ambient temperature smoke control (Sa) and medium temperature smoke control (S200) classifications;
—   ability to close and durability of self-closing (C0 – C5);
—   glazed elements;
—   side, transom or over panels;
—   items of building hardware;
—   decorative and protective finishes;
—   intumescent seals and non-intumescent (e.g. smoke, draught or acoustic) seals;
—   alternative supporting construction(s).
This document does not apply to horizontal doorsets and windows.

  • Standard
    120 pages
    English language
    e-Library read for
    ×1 day

This document is applicable to all coverings, including but not limited to renderings, boards with and without air gaps and installed with various support systems. This document specifies a method for determining the ability of a covering to protect underlying materials against damage during a specified fire exposure.
The document is not used for the evaluation of fire resistance classifications (e.g. EI, EW, E) or reaction to fire classifications (specified in EN 13501-1).
The fire protection ability is influenced by the presence of combustible materials in the cavity behind the covering. The applicability of the results is limited according to the quantity and position of such combustible materials within that cavity.
NOTE   The amount of combustible materials permissible in the cavity is generally laid down in national regulations.

  • Standard
    32 pages
    English language
    e-Library read for
    ×1 day

This document specifies a test method for determining the fire resistance of various elements of construction when subjected to fire exposure conditions, represented with standardized time-temperature curves. The test data thus obtained will permit subsequent classification on the basis of the duration for which the performance of the tested elements under these conditions satisfies specified criteria.

  • Standard
    54 pages
    English language
    e-Library read for
    ×1 day
  • Standard
    48 pages
    English language
    sale 15% off
  • Standard
    54 pages
    French language
    sale 15% off
  • Standard
    54 pages
    French language
    sale 15% off

This document is applicable to hinged and pivoted doors, doorsets and door assemblies with glass based leaves. Throughout this document the term “doorset” will be used to cover doors, doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1 and/or EN 1634-3 and/or EN 1191.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
—   integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
—   ambient temperature smoke control (Sa) and medium temperature smoke control (S200) classifications;
—   ability to close and durability of self-closing (C0 – C5);
—   glazed elements;
—   side, transom or over panels;
—   items of building hardware;
—   decorative and protective finishes;
—   intumescent seals and non-intumescent (e.g. smoke, draught or acoustic) seals;
—   alternative supporting construction(s).
This document does not apply to horizontal doorsets and windows.

  • Standard
    120 pages
    English language
    e-Library read for
    ×1 day

This document is applicable to all coverings, including but not limited to renderings, boards with and without air gaps and installed with various support systems. This document specifies a method for determining the ability of a covering to protect underlying materials against damage during a specified fire exposure.
The document is not used for the evaluation of fire resistance classifications (e.g. EI, EW, E) or reaction to fire classifications (specified in EN 13501-1).
The fire protection ability is influenced by the presence of combustible materials in the cavity behind the covering. The applicability of the results is limited according to the quantity and position of such combustible materials within that cavity.
NOTE   The amount of combustible materials permissible in the cavity is generally laid down in national regulations.

  • Standard
    32 pages
    English language
    e-Library read for
    ×1 day

This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE   EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.

  • Corrigendum
    2 pages
    English language
    e-Library read for
    ×1 day

1.1   Scope of EN 1995-1-2
(1) This document deals with the design of timber structures for the accidental situation of fire exposure and it is intended to be used in conjunction with EN 1995-1-1 and EN 1991-1-2.
This document only identifies differences from, or supplements to, normal temperature design.
(2) This document applies to timber structures required to fulfil a loadbearing function, separating function or both.
(3) This document gives principles and application rules for the design of structures for specified requirements in respect of the aforementioned functions and the levels of performance.
(4) This document applies to structures, or parts of structures, that are within the scope of EN 1995-1-1 and are designed accordingly.
(5) The methods given in this document are applicable to all products covered by European technical product specifications made reference to in this document.
1.2   Assumptions
(1) In addition to the general assumptions of EN 1990, the following assumptions apply:
-   the choice of the relevant design fire scenario is made by appropriate qualified and experienced personnel, or is given by the relevant national regulation;
-   any fire protection measure taken into account in the design will be adequately maintained.

  • Draft
    180 pages
    English language
    e-Library read for
    ×1 day

This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE   EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.

  • Corrigendum
    2 pages
    English language
    e-Library read for
    ×1 day

This document gives precisions on the mounting and fixing rules for testing glass products and provides guidance. It defines procedures for extended application of test results obtained in accordance with EN ISO 1716, EN ISO 11925 2, EN ISO 1182 and EN 13823 and classified according to EN 13501 1.
The extended application rules in this document are not applicable to laminated glass comprising plastic glazing sheet material.
This document is not applicable to joints and cables, junction boxes, glues, mounting seals and any fixing devices used to install the glass product.

  • Standard
    13 pages
    English language
    e-Library read for
    ×1 day

This document specifies the procedure for classification of the resistance to fire performance of construction products and building elements used as components of building service installations, using data from fire resistance tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
Construction products or building elements for use in ventilation systems include (excluding smoke control system):
—   fire resisting ventilation ducts;
—   fire dampers.
Construction products or building elements for use in or as cables systems:
—   unprotected electric cables with intrinsic fire resistance;
—   fire protective systems for cable systems and associated components.
Relevant test methods which have been prepared for these construction products/building elements are listed in Clause 2.
NOTE   Cables associated with fire dampers are not generally covered by this document unless there is a local regulation that requires it.

  • Standard
    29 pages
    English language
    e-Library read for
    ×1 day

This document specifies the procedure for classification of the resistance to fire performance of construction products and building elements used as components of building service installations, using data from fire resistance tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
Construction products or building elements for use in ventilation systems include (excluding smoke control system):
—   fire resisting ventilation ducts;
—   fire dampers.
Construction products or building elements for use in or as cables systems:
—   unprotected electric cables with intrinsic fire resistance;
—   fire protective systems for cable systems and associated components.
Relevant test methods which have been prepared for these construction products/building elements are listed in Clause 2.
NOTE   Cables associated with fire dampers are not generally covered by this document unless there is a local regulation that requires it.

  • Standard
    29 pages
    English language
    e-Library read for
    ×1 day

This document gives precisions on the mounting and fixing rules for testing glass products and provides guidance. It defines procedures for extended application of test results obtained in accordance with EN ISO 1716, EN ISO 11925 2, EN ISO 1182 and EN 13823 and classified according to EN 13501 1.
The extended application rules in this document are not applicable to laminated glass comprising plastic glazing sheet material.
This document is not applicable to joints and cables, junction boxes, glues, mounting seals and any fixing devices used to install the glass product.

  • Standard
    13 pages
    English language
    e-Library read for
    ×1 day

This document specifies the procedures to be followed for determining the fire resistance of columns when tested on their own. Two methods of testing are described: — Method A, which is applicable to any type of column and in which the test is conducted with an applied axial load to the column; and — Method B, which is only applicable to protected steel columns with any type of protection system and in which the test is conducted with no load applied to the column and the fire resistance is determined based on steel temperature limits. Method B is only applicable to protection systems that do not support any of the structural load. (See A.6). The application of this test to other untested forms of construction is acceptable when the construction conforms to the direct field of application as given in Annex B of this document, or when subjected to an extended application analysis in accordance with ISO/TR 12470 (series)[ REF Reference_ref_3 \r \h 1 08D0C9EA79F9BACE118C8200AA004BA90B0200000008000000100000005200650066006500720065006E00630065005F007200650066005F0033000000 ]. General guidance on test method A and test method B is given in Annex A.

  • Standard
    13 pages
    English language
    sale 15% off

This document, used in conjunction with ISO 834-1, specifies a method for determining the fire resistance of door and shutter assemblies designed primarily for installation within openings incorporated in vertical separating elements, such as: — hinged and pivoted doors, — horizontally sliding and vertically sliding doors, including articulated sliding doors and sectional doors, — steel single-skin folding shutters (un-insulated), — other sliding, folding doors, — tilting doors, — rolling shutter doors, — removable panels in walls, — self-closing openable windows. Requirements are included for mechanical pre-conditioning, e.g. “cycling” of door and shutter assemblies prior to the conduct of the fire-resistance test. This document does not cover: — Lift landing doors which are tested in accordance with ISO 3008-2.

  • Standard
    52 pages
    English language
    sale 15% off

This document specifies a test method for determining the fire resistance of various elements of construction when subjected to fire exposure conditions, represented with standardized time-temperature curves. The test data thus obtained will permit subsequent classification on the basis of the duration for which the performance of the tested elements under these conditions satisfies specified criteria.

  • Standard
    54 pages
    English language
    e-Library read for
    ×1 day
  • Standard
    48 pages
    English language
    sale 15% off
  • Standard
    54 pages
    French language
    sale 15% off
  • Standard
    54 pages
    French language
    sale 15% off

This document provides three examples of the use of reaction-to-fire test data for fire safety engineering (FSE).

  • Technical report
    42 pages
    English language
    sale 15% off

This document specifies test methods for cable management systems (CMS) intended to provide support for intrinsic fire-resistant cables in order to determine their abilities to maintain the function of electrical power cables and signal/control cables for a specified duration when subjected to fire under defined conditions.
This document establishes a non-hierarchical classification for this ability.
Additional devices to fix the cable management systems providing fire resistant support (CMS-support) to the building structure for example screws, anchors etc. are not covered by this document.
CMS intended to provide support and fire protection for cables are tested according to EN 1366-11.
This document does not apply to powertrack systems.
NOTE   Rules for testing CMS-support for fibre optic cables according to EN 50582 and communication cables according to EN 50289-4-16 are under consideration.

  • Technical specification
    53 pages
    English language
    e-Library read for
    ×1 day

This document specifies test methods for cable management systems (CMS) intended to provide support for intrinsic fire-resistant cables in order to determine their abilities to maintain the function of electrical power cables and signal/control cables for a specified duration when subjected to fire under defined conditions. This document establishes a non-hierarchical classification for this ability. Additional devices to fix the cable management systems providing fire resistant support (CMS-support) to the building structure for example screws, anchors etc. are not covered by this document. CMS intended to provide support and fire protection for cables are tested according to EN 1366-11. This document does not apply to powertrack systems. NOTE Rules for testing CMS-support for fibre optic cables according to EN 50582 and communication cables according to EN 50289-4-16 are under consideration.

  • Technical specification
    53 pages
    English language
    e-Library read for
    ×1 day

This test method specifies methods for determining the fire resistance of open-state cavity barriers and is to be used in conjunction with EN 1363-1.
This document is applicable to non-loadbearing vertically or horizontally oriented open-state cavity barriers, which are designed to close and provide fire separation in the event of fire.
Open-state cavity barriers in facades, where the fire exposure comes as a result of a breaking window and allowing a developed fire to come into contact with the façade, can be tested to the optional "flame" criteria.
This document is not applicable to cavity barriers containing penetration seals, which are covered by EN 1366-3.
This document is not applicable to closed cavity barriers, which are covered by EN 1366-4.

  • Standard
    18 pages
    English language
    e-Library read for
    ×1 day

This test method specifies methods for determining the fire resistance of open-state cavity barriers and is to be used in conjunction with EN 1363-1.
This document is applicable to non-loadbearing vertically or horizontally oriented open-state cavity barriers, which are designed to close and provide fire separation in the event of fire.
Open-state cavity barriers in facades, where the fire exposure comes as a result of a breaking window and allowing a developed fire to come into contact with the façade, can be tested to the optional "flame" criteria.
This document is not applicable to cavity barriers containing penetration seals, which are covered by EN 1366-3.
This document is not applicable to closed cavity barriers, which are covered by EN 1366-4.

  • Standard
    18 pages
    English language
    e-Library read for
    ×1 day

This document describes an extended test method determining the resistance to jet fires of passive fire protection (PFP) materials and systems or critical process control equipment. It gives an indication of how PFP material or equipment behaves in a severe jet fire and provides performance data under the specified conditions. It does not include an assessment of other properties of the passive fire protection material such as weathering, ageing, shock resistance, impact or explosion resistance, or smoke production. This document is intended to be complementary to ISO 22899-1. It is intended for use in situations when the required fire conditions or limitations on test specimen size or type preclude application of ISO 22899-1.

  • Standard
    38 pages
    English language
    sale 15% off

This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE   EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.

  • Standard
    194 pages
    English language
    e-Library read for
    ×1 day

This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE   EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.

  • Standard
    194 pages
    English language
    e-Library read for
    ×1 day

This document covers single and double leaf, hinged and pivoted, steel based doorsets except steel doorsets with metal framed door leaves covered by EN 15269-5. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
-   integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
-   door leaf;
-   side panels, transom panels, flush overpanels;
-   air transfer grilles (e.g. ventilation grilles/louvres);
-   components (e.g. frame/suspension system) fixed to the supporting construction (e.g. wall/ceiling);
-   glazing within the doorset (e.g. for door leaf, side, transom and flush overpanels);
-   items of building hardware;
-   decorative and protective finishes;
-   intumescent seals, strips and non-intumescent (smoke, draught or acoustic) seals;
-   alternative supporting construction(s).
This document does not cover horizontally installed doorsets (e.g. traps).
The effect on the classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

  • Standard
    141 pages
    English language
    e-Library read for
    ×1 day

This document covers single and double leaf, hinged and pivoted, steel based doorsets except steel doorsets with metal framed door leaves covered by EN 15269-5. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
-   integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
-   door leaf;
-   side panels, transom panels, flush overpanels;
-   air transfer grilles (e.g. ventilation grilles/louvres);
-   components (e.g. frame/suspension system) fixed to the supporting construction (e.g. wall/ceiling);
-   glazing within the doorset (e.g. for door leaf, side, transom and flush overpanels);
-   items of building hardware;
-   decorative and protective finishes;
-   intumescent seals, strips and non-intumescent (smoke, draught or acoustic) seals;
-   alternative supporting construction(s).
This document does not cover horizontally installed doorsets (e.g. traps).
The effect on the classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

  • Standard
    141 pages
    English language
    e-Library read for
    ×1 day

This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.

  • Standard
    49 pages
    English language
    e-Library read for
    ×1 day