Standard Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Endurance Tests

SCOPE
1.1 This practice covers procedures for calculating the superimposed axial load required to be applied to load-bearing wood-frame walls throughout standard fire-endurance and fire and hose-stream tests.
1.2 The calculations determine the maximum load allowed by design for wood-frame wall assemblies under nationally recognized structural design criteria.
1.3 This practice is only applicable to those wood-frame assemblies for which the nationally recognized structural design criteria is the National Design Specification for Wood Construction (NDS).
1.4 The system of units to be used is that of the nationally recognized structural design criteria. For the NDS, the units are inch-pound.
1.5 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Feb-2000
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM D6513-00 - Standard Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Endurance Tests
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D6513–00
Standard Practice for
Calculating the Superimposed Load on Wood-frame Walls
for Standard Fire-Endurance Tests
This standard is issued under the fixed designation D 6513; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 2.2 Other Standards:
NDS—National Design Specification for Wood Construc-
1.1 This practice covers procedures for calculating the
tion
superimposed axial load required to be applied to load-bearing
NDS Supplement—Design Values for Wood Construction
wood-frame walls throughout standard fire-endurance and fire
and hose-stream tests.
3. Terminology
1.2 The calculations determine the maximum load allowed
3.1 Definitions—Definitions used in this practice are in
by design for wood-frame wall assemblies under nationally
accordance with Terminology D 9 and Terminology E 176,
recognized structural design criteria.
unless otherwise indicated.
1.3 This practice is only applicable to those wood-frame
3.2 Definitions of Terms Specific to This Standard:
assemblies for which the nationally recognized structural
3.2.1 gross area, n—section area calculated from overall
design criteria is the National Design Specification for Wood
actual dimensions of member.
Construction (NDS).
3.2.2 net section area, n—sectionareacalculatedbydeduct-
1.4 The system of units to be used is that of the nationally
ing from the gross section area the projected area of all
recognizedstructuraldesigncriteria.FortheNDS,theunitsare
materials removed by boring, grooving, dapping, notching, or
inch-pound.
other means.
1.5 The text of this standard references notes and footnotes
3.2.3 superimposed load, n—The additional external load
which provide explanatory material. These notes and footnotes
needed to be applied to the assembly to result in the calculated
(excluding those in tables and figures) shall not be considered
stresses within the assembly when any dead load of the
as requirements of the standard.
assembly itself is accounted for in the calculations.
1.6 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
4. Significance and Use
responsibility of the user of this standard to establish appro-
4.1 Test Methods E 119 and E 1529, and other standard fire
priate safety and health practices and determine the applica-
endurance test methods specify that throughout exposures to
bility of regulatory limitations prior to use.
fire and the hose stream, a constant superimposed axial load be
2. Referenced Documents applied to a load-bearing test specimen to simulate a maximum
load condition. They specify that this superimposed load shall
2.1 ASTM Standards:
3 be as nearly as practicable the maximum load allowed by
D 9 Terminology Relating to Wood
design under nationally recognized structural design criteria.
E 119 Test Methods for Fire Tests of Building Construction
4 For this practice, the nationally recognized structural design
and Materials
4 criteria is the National Design Specification for Wood Con-
E 176 Terminology Relating to Fire Standards
struction (NDS).
E 1529 Test Methods for Determining Effects of Large
4.1.1 Alternatively, the standard fire endurance test methods
Hydrocarbon Pool Fires on Structural Members and As-
shall be conducted by applying an axial load that is less than
semblies
the maximum allowable axial load as addressed by the NDS
and this practice, but these tests shall be identified in the test
This practice is under the jurisdiction of ASTM Committee D-7 on Wood and report as being conducted under restricted load conditions.The
is the direct responsibility of Subcommittee D07.07 on Fire Performance of Wood
superimposed axial load, as well as the superimposed axial
Products.
load as a percentage of the maximum allowable axial design
Current edition approved Feb. 10, 2000. Published April 2000.
load as addressed by the NDS and this practice shall be
Available from American Forest & Paper Association, American Wood Coun-
cil, 1111 19th Street, NW, Suite 800, Washington, DC 20036
included in the test report.
Annual Book of ASTM Standards, Vol 04.10.
Annual Book of ASTM Standards, Vol 04.07.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
D6513
4.2 This practice describes procedures for calculating the 6.2.7.1 Buckling of compression member in plane of wall is
superimposed axial load to be applied in standard fire endur- prevented by the sheathing which normally provides support
ance tests of wood-frame wall assemblies. throughout its length and C equals 1.
P
4.3 Statements in either the fire endurance test method 6.2.7.2 For buckling of compression member perpendicular
standardorthenationallyrecognizedstructuraldesignstandard to plane of wall, C depends on the slenderness ratio of the
P
supercede any procedures described by this practice. columns. The equation for C is given in the NDS. The
P
4.4 The NDS shall be consulted to ensure calculations are in effectivecolumnlengthshallbetheactuallengthofthevertical
compliance with all applicable provisions of that document. member for calculating the slenderness ratio and C .
P
6.2.8 Buckling stiffness factor, C , is 1.0.
T
5. Test Assumptions
6.2.9 Bearing area factor, C , is 1.0.
b
5.1 Wood-framewallsconsistofverticalcompressionmem-
NOTE 1—The NDS provides for a bearing area
...