D27.01 - Mineral
Mineral
General Information
SCOPE
1.1 This specification covers rerefined previously used mineral insulating liquid of petroleum origin for reuse as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, liquid filled circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a rerefined mineral insulating liquid that is functionally interchangeable and miscible with existing mineral insulating liquids, is compatible with existing apparatus, and with appropriate field maintenance2 will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to rerefined mineral insulating liquid as received prior to any processing. Liquids that undergo treatment in-situ are not covered by this specification.
1.3 Formulated rerefined mineral insulating liquids may contain additives such as inhibitors, passivators, pour point depressants, flow modifiers, gassing tendency modifiers, and other compounds. This specification will address some of these but not all. It is the responsibility of the supplier to disclose information concerning the presence of all known additives and their concentration to the user.
1.4 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification6 pagesEnglish language
ABSTRACT
This specification describes a high fire-point mineral oil based electrical insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatuses, such as transformers and switchgear. The material discussed here is miscible with other petroleum based insulating oils, and may not be miscible with electrical insulating liquids of non-petroleum origin. The insulating oils shall be compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application. This specification applies only to new insulating material oil as received prior to any processing. Sampled specimens shall undergo appropriate tests, and shall conform correspondingly to specified physical (appearance upon visual examination, color in ASTM units, fire point, flash point, aniline point, interfacial tension, pour point, relative density, and kinematic viscosity), electrical (dielectric breakdown voltage, gassing tendency, and dissipation factor), and chemical (corrosion behavior against sulfur, inorganic chlorides and sulfates content, acid number, water content, oxidation stability, oxidation inhibitor content, and PCB content) property requirements.
SCOPE
1.1 This specification describes a less flammable mineral electrical insulating liquid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatus, such as transformers and switchgear.
1.2 Less flammable insulating liquid differs from conventional mineral insulating liquid by possessing a fire-point of at least 300 °C. This property is necessary in order to comply with certain application requirements of the National Electrical Code (Article 450-23) or other agencies. The material discussed in this specification is miscible with other petroleum based insulating liquids. Mixing less flammable liquids with lower fire point hydrocarbon insulating liquids (for example, Specification D3487 mineral liquid) may result in fire points of less than 300 °C.
1.3 This specification is intended to define a less flammable electrical mineral insulating liquid that is compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in this application. The material described in this specification may not be miscible with electrical insulating liquids of non-petroleum origin. The user should contact the manufacturer of the less flammable insulating liquid for guidance in this respect.
1.4 This specification applies only to new electrical insulating liquid as received prior to any processing. Information on in-service maintenance testing is available in appropriate guides.2 The user should contact the manufacturers of the equipment or liquid if questions of recommended characteristics or maintenance procedures arise.
1.5 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification3 pagesEnglish language
- Technical specification3 pagesEnglish language
ABSTRACT
This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both. This guide is classified into the following categories: sampling practices, physical tests, electrical tests, chemical tests, and specifications. The test methods shall be as follows: aniline point; coefficient of thermal expansion; color; examination; flash and fire point; interfacial tension; pour point of petroleum products; refractive index; relative density; specific heat; thermal conductivity; turbidity; viscosity; dielectric breakdown voltage; dissipation factor and relative permittivity; gassing tendency; resistivity; stability under electrical discharge; acidity; carbon-type composition; compatibility with construction material; copper content; furanic compounds; gas analysis; gas content; inorganic chlorides and sulfates; neutralization numbers; oxidation inhibitor content; oxidation stability; polychlorinated biphenyl content; sediment and soluble sludge; sulfur; water content; mineral insulating oil for electrical apparatus; and high firepoint electrical insulating oils.
SCOPE
1.1 This guide describes methods of testing and specifications for electrical insulating liquids intended for use in electrical cables, transformers, liquid-filled circuit breakers, and other electrical apparatus where the liquids are used as insulating, or heat transfer media, or both.
1.2 The purpose of this guide is to outline the applicability of the available test methods. Where more than one is available for measuring a given property, their relative advantages are described, along with an indication of laboratory convenience, precision, (95 % confidence limits), and applicability to specific types of electrical insulating liquids.
1.3 This guide is classified into the following categories: Sampling Practices, Physical Tests, Electrical Tests, Chemical Tests, and Specifications. Within each test category, the test methods are listed alphabetically by property measured. A list of standards follows:
Category
Section
ASTM Standard
Sampling:
3
D923
Physical Tests:
Aniline Point
4
D611
Coefficient of Thermal Ex-
pansion
5
D1903
Color
6
D1500
Examination: Visual Infrared
7
D1524, D2144, D2129
Flash and Fire Point
8
D92
Interfacial Tension
9
D971
Pour Point of Petroleum
Products
10
D97, D5949, D5950
Particle Count in Mineral
Insulating Oil
11
D6786
Refractive Index and Specific
Optical Dispersion
12
D1218
Relative Density (Specific
Gravity)
13
D287, D1217, D1298, D1481, D4052
Specific Heat
14
D2766
Thermal Conductivity
15
D2717
Viscosity
16
D445, D2161, D7042
Electrical Tests:
Dielectric Breakdown Voltage
17
D877, D1816, D3300
Dissipation Factor and Rela-
tive Permittivity (Dielectric
Constant)
18
D924
Gassing Characteristic
Under Thermal Stress
19
D7150
Gassing Tendency
20
D2300
Resistivity
21
D1169
Chemical Tests:
Acidity, Approximate
22
D1534
Carbon-Type Composition
23
D2140
Compatibility with Construc-
tion Material
24
D3455
Copper Content
25
D3635
Elements by Inductively
Coupled Plasma (ICP-AES)
26
D7151
Furanic Compounds in
Electrical Insulating Liquids
27
D5837
Dissolved Gas Analysis
28
D3612
Gas Content of Cable and
Capacitor Liquids
29
D831, D1827, D2945
Neutralization (Acid and
Base) Numbers
30
D664, D974
Oxidation Inhibitor Content
31
D2668, D4768
Oxidation Stability
32
D1934, D2112, D2440
P...
- Guide16 pagesEnglish language
- Guide16 pagesEnglish language
ABSTRACT
This specification covers two types of new mineral insulating oils of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatuses, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment. It is the intension of this specification to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. Type I mineral oils are used for apparatuses where normal oxidation resistance is required, where as, Type II mineral oils are used for apparatuses where greater oxidation resistance is required. When examined with corresponding test methods, sampled specimens shall conform accordingly to physical (aniline point, color, flash point, interfacial tension, pour point, relative density or specific gravity, viscosity, and appearance), electrical (dielectric breakdown voltage, gassing tendency, and dissipation or power factor), and chemical (oxidation stability, oxidation inhibitor content, corrosive sulfur content, water content, neutralization number, and PCB content) property requirements.
SCOPE
1.1 This specification covers unused mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance,2 and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification6 pagesEnglish language
ABSTRACT
This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both. This guide is classified into the following categories: sampling practices, physical tests, electrical tests, chemical tests, and specifications. The test methods shall be as follows: aniline point; coefficient of thermal expansion; color; examination; flash and fire point; interfacial tension; pour point of petroleum products; refractive index; relative density; specific heat; thermal conductivity; turbidity; viscosity; dielectric breakdown voltage; dissipation factor and relative permittivity; gassing tendency; resistivity; stability under electrical discharge; acidity; carbon-type composition; compatibility with construction material; copper content; furanic compounds; gas analysis; gas content; inorganic chlorides and sulfates; neutralization numbers; oxidation inhibitor content; oxidation stability; polychlorinated biphenyl content; sediment and soluble sludge; sulfur; water content; mineral insulating oil for electrical apparatus; and high firepoint electrical insulating oils.
SCOPE
1.1 This guide describes methods of testing and specifications for electrical insulating liquids intended for use in electrical cables, transformers, liquid circuit breakers, and other electrical apparatus where the liquids are used as insulating, or heat transfer media, or both.
1.2 The purpose of this guide is to outline the applicability of the available test methods. Where more than one is available for measuring a given property, their relative advantages are described, along with an indication of laboratory convenience, precision, (95 % confidence limits), and applicability to specific types of electrical insulating oils.
1.3 This guide is classified into the following categories: Sampling Practices, Physical Tests, Electrical Tests, Chemical Tests, and Specifications. Within each test category, the test methods are listed alphabetically by property measured. A list of standards follows:
Category
Section
ASTM Standard
Sampling:
3
D923
Physical Tests:
Aniline Point
4
D611
Coefficient of Thermal Ex-
pansion
5
D1903
Color
6
D1500
Examination: Visual Infrared
7
D1524, D2144, D2129
Flash and Fire Point
8
D92
Interfacial Tension
9
D971, D2285
Pour Point of Petroleum
Products
10
D97, D5949, D5950
Particle Count in Mineral
Insulating Oil
11
D6786
Refractive Index and Specific
Optical Dispersion
12
D1218, D1807
Relative Density (Specific
Gravity)
13
D287, D1217, D1298, D1481, D4052
Specific Heat
14
D2766
Thermal Conductivity
15
D2717
Turbidity
16
D6181
Viscosity
17
D445, D2161
Electrical Tests:
Dielectric Breakdown Voltage
18
D877, D1816, D3300
Dissipation Factor and Rela-
tive Permittivity (Dielectric
Constant)
19
D924
Gassing Characteristic
Under Thermal Stress
20
D7150
Gassing Tendency
21
D2300
Resistivity
22
D1169
Stability Under Electrical
Discharge
23
D6180
Chemical Tests:
Acidity, Approximate
24
D1534
Carbon-Type Composition
25
D2140
Compatibility with Construc-
tion Material
26
D3455
Copper Content
27
D3635
Elements by Inductively
Coupled Plasma (ICP-AES)
28
D7151
Furanic Compounds in
Electrical Insulating Liquids
29
D5837
Dissolved Gas Analysis
30
D3612
Gas Content of Cable and
Capacitor Oils
31
D831, D1827, D2945
Inorganic Chlorides and
Sulfates
32
D878
Neutralization (Acid and
Base) Numbe...
- Guide17 pagesEnglish language
- Guide17 pagesEnglish language
ABSTRACT
This specification describes a high fire-point mineral oil based electrical insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatuses, such as transformers and switchgear. The material discussed here is miscible with other petroleum based insulating oils, and may not be miscible with electrical insulating liquids of non-petroleum origin. The insulating oils shall be compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application. This specification applies only to new insulating material oil as received prior to any processing. Sampled specimens shall undergo appropriate tests, and shall conform correspondingly to specified physical (appearance upon visual examination, color in ASTM units, fire point, flash point, aniline point, interfacial tension, pour point, relative density, and kinematic viscosity), electrical (dielectric breakdown voltage, gassing tendency, and dissipation factor), and chemical (corrosion behavior against sulfur, inorganic chlorides and sulfates content, acid number, water content, oxidation stability, oxidation inhibitor content, and PCB content) property requirements.
SCOPE
1.1 This specification describes a high fire-point mineral oil based insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatus, such as transformers and switchgear.
1.2 High fire-point insulating oil differs from conventional mineral insulating oil by possessing a fire-point of at least 300°C. High fire-point mineral insulating oils are also referred to as “less flammable” mineral insulating oils.This property is necessary in order to comply with certain application requirements of the National Electrical Code (Article 450-23) or other agencies. The material discussed in this specification is miscible with other petroleum based insulating oils. Mixing high fire-point liquids with lower fire point hydrocarbon insulating oils (for example, Specification D3487 mineral oil) may result in fire points of less than 300°C.
1.3 This specification is intended to define a high fire-point electrical mineral insulating oil that is compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application in this application. The material described in this specification may not be miscible with electrical insulating liquids of non-petroleum origin. The user should contact the manufacturer of the high fire-point insulating oil for guidance in this respect.
1.4 This specification applies only to new insulating material oil as received prior to any processing. Information on in-service maintenance testing is available in appropriate guides.2 The user should contact the manufacturers of the equipment or oil if questions of recommended characteristics or maintenance procedures arise.
1.5 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
- Technical specification3 pagesEnglish language
- Technical specification3 pagesEnglish language
ABSTRACT
This specification covers two types of new mineral insulating oils of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatuses, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment. It is the intension of this specification to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. Type I mineral oils are used for apparatuses where normal oxidation resistance is required, where as, Type II mineral oils are used for apparatuses where greater oxidation resistance is required. When examined with corresponding test methods, sampled specimens shall conform accordingly to physical (aniline point, color, flash point, interfacial tension, pour point, relative density or specific gravity, viscosity, and appearance), electrical (dielectric breakdown voltage, gassing tendency, and dissipation or power factor), and chemical (oxidation stability, oxidation inhibitor content, corrosive sulfur content, water content, neutralization number, and PCB content) property requirements.
SCOPE
1.1 This specification covers unused mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance,2 and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
- Technical specification5 pagesEnglish language
- Technical specification5 pagesEnglish language
ABSTRACT
This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both. This guide is classified into the following categories: sampling practices, physical tests, electrical tests, chemical tests, and specifications. The test methods shall be as follows: aniline point; coefficient of thermal expansion; color; examination; flash and fire point; interfacial tension; pour point of petroleum products; refractive index; relative density; specific heat; thermal conductivity; turbidity; viscosity; dielectric breakdown voltage; dissipation factor and relative permittivity; gassing tendency; resistivity; stability under electrical discharge; acidity; carbon-type composition; compatibility with construction material; copper content; furanic compounds; gas analysis; gas content; inorganic chlorides and sulfates; neutralization numbers; oxidation inhibitor content; oxidation stability; polychlorinated biphenyl content; sediment and soluble sludge; sulfur; water content; mineral insulating oil for electrical apparatus; and high firepoint electrical insulating oils.
SCOPE
1.1 This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both.
1.2 The purpose of this guide is to outline the applicability of the available test methods. Where more than one is available for measuring a given property, their relative advantages are described, along with an indication of laboratory convenience, precision, (95 % confidence limits), and applicability to specific types of electrical insulating oils.
- Guide16 pagesEnglish language
- Guide16 pagesEnglish language
ABSTRACT
This specification covers two types of new mineral insulating oils of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment. It is the intension of this specification to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. Type I mineral oils are used for apparatus where normal oxidation resistance is required, where as, Type II mineral oils are used for apparatus where greater oxidation resistance is required. When examined with corresponding test methods, sampled specimens shall conform accordingly to physical (aniline point, color, flash point, interfacial tension, pour point, relative density or specific gravity, viscosity, and appearance), electrical (dielectric breakdown voltage, gassing tendency, and dissipation or power factor), and chemical (oxidation stability, oxidation inhibitor content, corrosive sulfur content, water content, neutralization number, and PCB content) property requirements.
SCOPE
1.1 This specification covers new mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
- Technical specification5 pagesEnglish language
- Technical specification5 pagesEnglish language
ABSTRACT
This specification covers two types of new mineral insulating oils of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment. It is the intension of this specification to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. Type I mineral oils are used for apparatus where normal oxidation resistance is required, where as, Type II mineral oils are used for apparatus where greater oxidation resistance is required. When examined with corresponding test methods, sampled specimens shall conform accordingly to physical (aniline point, color, flash point, interfacial tension, pour point, relative density or specific gravity, viscosity, and appearance), electrical (dielectric breakdown voltage, gassing tendency, and dissipation or power factor), and chemical (oxidation stability, oxidation inhibitor content, corrosive sulfur content, water content, neutralization number, and PCB content) property requirements.
SCOPE
1.1 This specification covers new mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
- Technical specification5 pagesEnglish language
- Technical specification5 pagesEnglish language
- Technical specification5 pagesEnglish language
ABSTRACT
This specification describes a high fire-point mineral oil based electrical insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatus, such as transformers and switchgear. The material discussed here is miscible with other petroleum based insulating oils, and may not be miscible with electrical insulating liquids of non-petroleum origin. The insulating oils shall be compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application. This specification applies only to new insulating material oil as received prior to any processing. Sampled specimens shall undergo appropriate tests, and shall conform correspondingly to specified physical (appearance upon visual examination, color in ASTM units, fire point, flash point, aniline point, interfacial tension, pour point, relative density, and kinematic viscosity), electrical (dielectric breakdown voltage, gassing tendency, and dissipation factor), and chemical (corrosion behavior against sulfur, inorganic chlorides and sulfates content, acid number, water content, oxidation stability, oxidation inhibitor content, and PCB content) property requirements.
SCOPE
1.1 This specification describes a high fire-point mineral oil based insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatus, such as transformers and switchgear.
1.2 High fire-point insulating oil differs from conventional mineral insulating oil by possessing a fire-point of at least 300°C. High fire-point mineral insulating oils are also referred to as “less flammable” mineral insulating oils.This property is necessary in order to comply with certain application requirements of the National Electrical Code (Article 450-23) or other agencies. The material discussed in this specification is miscible with other petroleum based insulating oils. Mixing high fire-point liquids with lower fire point hydrocarbon insulating oils (for example, Specification D 3487 mineral oil) may result in fire points of less than 300°C.
1.3 This specification is intended to define a high fire-point electrical mineral insulating oil that is compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application in this application. The material described in this specification may not be miscible with electrical insulating liquids of non-petroleum origin. The user should contact the manufacturer of the high fire-point insulating oil for guidance in this respect.
1.4 This specification applies only to new insulating material oil as received prior to any processing. Information on in-service maintenance testing is available in appropriate guides. The user should contact the manufacturers of the equipment or oil if questions of recommended characteristics or maintenance procedures arise.
- Technical specification3 pagesEnglish language
- Technical specification3 pagesEnglish language
ABSTRACT
This specification covers two types of new mineral insulating oils of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment. It is the intension of this specification to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. Type I mineral oils are used for apparatus where normal oxidation resistance is required, where as, Type II mineral oils are used for apparatus where greater oxidation resistance is required. When examined with corresponding test methods, sampled specimens shall conform accordingly to physical (aniline point, color, flash point, interfacial tension, pour point, relative density or specific gravity, viscosity, and appearance), electrical (dielectric breakdown voltage, gassing tendency, and dissipation or power factor), and chemical (oxidation stability, oxidation inhibitor content, corrosive sulfur content, water content, neutralization number, and PCB content) property requirements.
SCOPE
1.1 This specification covers new mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
- Technical specification5 pagesEnglish language
ABSTRACT
This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both. This guide is classified into the following categories: sampling practices, physical tests, electrical tests, chemical tests, and specifications. The test methods shall be as follows: aniline point; coefficient of thermal expansion; color; examination; flash and fire point; interfacial tension; pour point of petroleum products; refractive index; relative density; specific heat; thermal conductivity; turbidity; viscosity; dielectric breakdown voltage; dissipation factor and relative permittivity; gassing tendency; resistivity; stability under electrical discharge; acidity; carbon-type composition; compatibility with construction material; copper content; furanic compounds; gas analysis; gas content; inorganic chlorides and sulfates; neutralization numbers; oxidation inhibitor content; oxidation stability; polychlorinated biphenyl content; sediment and soluble sludge; sulfur; water content; mineral insulating oil for electrical apparatus; and high firepoint electrical insulating oils.
SCOPE
1.1 This guide describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating, or heat transfer media, or both.
1.2 The purpose of this guide is to outline the applicability of the available test methods. Where more than one is available for measuring a given property, their relative advantages are described, along with an indication of laboratory convenience, precision, (95 % confidence limits), and applicability to specific types of electrical insulating oils.
1.3 This guide is classified into the following categories: Sampling Practices, Physical Tests, Electrical Tests, Chemical Tests, and Specifications. Within each test category, the test methods are listed alphabetically by property measured. A list of standards follows:CategorySectionASTM MethodSampling: 3D 923, D2759, D3305, D3613Physical Tests: Aniline Point4D 611Coefficient of Thermal Expansion5D 1903Color6D 1500Examination: Visual Infrared7D 1524, D2144Flash and Fire Point8D 92Interfacial Tension9D 971, D2285Pour Point of PetroleumProducts10D 97Refractive Index11D 1218, D1807Relative Density (SpecificGravity)12D 287, D 1217, D1298, D1481Specific Heat13D 2766Thermal Conductivity14D 2717Turbidity15D 6181Viscosity16D 88, D445, D2161Electrical Tests:Dielectric Breakdown Voltage17D 877, D1816, D3300Dissipation Factor and Rela-tive Permittivity (Dielectric Constant)18D 924Gassing Tendency19D 2300Resistivity20D 1169Stability Under Electrical Discharge21D 6180Chemical Tests:Acidity, Approximate22D 1534Carbon-Type Composition23D 2140Compatibility with Construction Material24D 3455Copper Content25D 3635Furanic Compounds26D 5837Gas Analysis27D 3612Gas Content28D 831, D1827, D2945Inorganic Chlorides and Sulfates29D 878Neutralization (Acid andBase) Numbers30D 664, D974Oxidation Inhibitor Content31D 2668, D4768Oxidation Stability32D 1934, D2112, D2440Polychlorinated BiphenylContent33D 4059Sediment and Soluble Sludge34D 1698Sulfur, Corrosive35D 1275Water Content36D 1533Specification:Mineral Insulating Oil forElectrical Apparatus37D 3487High Firepoint Electrical Insulating Oils38D 5222
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Guide14 pagesEnglish language
SCOPE
1.1 This specification covers new mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as, transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
- Technical specification5 pagesEnglish language
SCOPE
1.1 This specification covers new mineral insulating oil of petroleum origin for use as an insulating and cooling medium in new and existing power and distribution electrical apparatus, such as, transformers, regulators, reactors, circuit breakers, switchgear, and attendant equipment.
1.2 This specification is intended to define a mineral insulating oil that is functionally interchangeable and miscible with existing oils, is compatible with existing apparatus and with appropriate field maintenance, and will satisfactorily maintain its functional characteristics in its application in electrical equipment. This specification applies only to new insulating oil as received prior to any processing.
- Technical specification5 pagesEnglish language
SCOPE
1.1 This specification describes a high fire-point mineral oil based insulating fluid, for use as a dielectric and cooling medium in new and existing power and distribution electrical apparatus, such as transformers and switchgear.
1.2 High fire-point insulating oil differs from conventional mineral insulating oil by possessing a fire-point of at least 300oC. High fire-point mineral insulating oils are also referred to as "less flammable" mineral insulating oils.This property is necessary in order to comply with certain application requirements of the National Electrical Code (Article 450-23) or other agencies. The material discussed in this specification is miscible with other petroleum based insulating oils. Mixing high fire-point liquids with lower fire point hydrocarbon insulating oils (for example, Specification D3487 mineral oil) may result in fire points of less than 300oC.
1.3 This specification is intended to define a high fire-point electrical mineral insulating oil that is compatible with typical material of construction of existing apparatus and will satisfactorily maintain its functional characteristic in its application in this application. The material described in this specification may not be miscible with electrical insulating liquids of non-petroleum origin. The user should contact the manufacturer of the high fire-point insulating oil for guidance in this respect.
1.4 This specification applies only to new insulating material oil as received prior to any processing. Information on in-service maintenance testing is available in appropriate guides. The user should contact the manufacturers of the equipment or oil if questions of recommended characteristics or maintenance procedures arise.
- Technical specification3 pagesEnglish language
SCOPE
1.1 This standard describes methods of testing and specifications for electrical insulating oils of petroleum origin intended for use in electrical cables, capacitors, transformers, oil circuit breakers, and other electrical apparatus where the oils are used as insulating or heat transfer media, or both.
1.2 The purpose of this standard is to outline the applicability of the available test methods. Where more than one is available for measuring a given property, their relative advantages are described, along with an indication of laboratory convenience, precision, (95% confidence limits), and applicability to specific types of electrical insulating oils.
1.3 The guide is classified into the following categories: Sampling, Physical Tests, Electrical Tests, Chemical Tests, Specifications, and Guide. Within each test category, the test methods are listed alphabetically by property measured.
1.4 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.>
- Guide13 pagesEnglish language
Frequently Asked Questions
D27.01 is a Technical Committee within ASTM International. It is named "Mineral". This committee has published 17 standards.
D27.01 develops ASTM standards in the area of Information technology. Currently, there are 17 published standards from this technical committee.
ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.
A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.