SIST EN 13823:2002
(Main)Reaction to fire tests for building products - Building products excluding floorings exposed to the thermal attack by a single burning item
Reaction to fire tests for building products - Building products excluding floorings exposed to the thermal attack by a single burning item
This European Standard specifies a method of test for determining the reaction to fire performance of construction products excluding floorings, and excluding products which are indicated in the EC Decision 2000/147/EC, when exposed to thermal attack by a single burning item (SBI). The calculation procedures are given in annex A. Information on the precision of the test method is given in annex B. The calibration procedures are given in annexes C and D, of which C is a normative annex.
NOTE This European Standard has been developed to determine the reaction to fire performance of essentially flat products. The treatment of some families of products, e.g. linear products (pipes, ducts, cables etc) can need special rules.
Prüfungen zum Brandverhalten von Bauprodukten - Thermische Beanspruchung durch einen einzelnen brennenden Gegenstand für Bauprodukte mit Ausnahme von Bodenbelägen
Diese Europäische Norm beschreibt ein Prüfverfahren zur Bestimmung des Brandverhaltens von Bauprodukten bei thermischer Beanspruchung durch einen einzelnen brennenden Gegenstand (SBI: ¿Single Burning Item"), ausgenommen Bodenbeläge sowie Bauprodukte, die in der Entscheidung der Kommission 2000/147/EG aufgeführt sind. Die Berechnungsverfahren sind Anhang A zu entnehmen. Informationen zur Genauigkeit des Prüfverfahrens sind in Anhang B zu finden. Die Kalibrierverfahren sind Anhang C und Anhang D zu entnehmen, wobei Anhang C normativ ist.
ANMERKUNG Diese Europäische Norm wurde erstellt, um das Brandverhaltens von im Wesentlichen ebenen Bauprodukten festzustellen. Die Behandlung von einigen Produktfamilien, z.B. lineare Bauprodukte (Rohre, Lüftungsleitungen, Kabel u.s.w.) können besondere Regeln erfordern.
Essais de réaction au feu des produits de construction - Produits de construction a l'exclusion des revetements de sol exposés a une sollicitation thermique provoquée par un objet isolé en feu
La présente Norme européenne définit une méthode d'essai de détermination de la performance de réaction au feu des produits de construction, à l'exception des revêtements de sol et des produits figurant dans la Décision CE 2000/147/CE, exposés à la sollicitation thermique provoquée par un « Single Burning Item » (SBI) (Objet Isolé en Feu) (OIF). Les méthodes de calcul sont fournies dans l'annexe A. Des informations relatives à la précision de la méthode d'essai sont données dans l'annexe B. Les méthodes d'étalonnage figurent dans les annexes C et D, C étant une annexe normative.
NOTE La présente Norme européenne a été élaborée pour déterminer la performance en réaction au feu de produits essentiellement plats. Le traitement de quelques familles de produits linéaires (tubes, conduits, câbles, etc.) peut nécessiter des règles particulières.
Preskusi odziva gradbenih proizvodov na ogenj - Gradbeni proizvodi razen talnih oblog, izpostavljeni toplotnemu delovanju enega samega gorečega predmeta
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2002
3UHVNXVLRG]LYDJUDGEHQLKSURL]YRGRYQDRJHQM*UDGEHQLSURL]YRGLUD]HQWDOQLK
REORJL]SRVWDYOMHQLWRSORWQHPXGHORYDQMXHQHJDVDPHJDJRUHþHJDSUHGPHWD
Reaction to fire tests for building products - Building products excluding floorings
exposed to the thermal attack by a single burning item
Prüfungen zum Brandverhalten von Bauprodukten - Thermische Beanspruchung durch
einen einzelnen brennenden Gegenstand für Bauprodukte mit Ausnahme von
Bodenbelägen
Essais de réaction au feu des produits de construction - Produits de construction a
l'exclusion des revetements de sol exposés a une sollicitation thermique provoquée par
un objet isolé en feu
Ta slovenski standard je istoveten z: EN 13823:2002
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 13823
NORME EUROPÉENNE
EUROPÄISCHE NORM
February 2002
ICS 13.220.50
English version
Reaction to fire tests for building products - Building products
excluding floorings exposed to the thermal attack by a single
burning item
Essais de réaction au feu des produits de construction - Prüfungen zum Brandverhalten von Bauprodukten -
Produits de construction à l'exclusion des revêtements de Thermische Beanspruchung durch einen einzelnen
sol exposés à une sollicitation thermique provoquée par un brennenden Gegenstand für Bauprodukte mit Ausnahme
objet isolé en feu von Bodenbelägen
This European Standard was approved by CEN on 16 November 2001.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2002 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13823:2002 E
worldwide for CEN national Members.
Contents
page
1 Scope 5
2 Normative references 6
3 Terms and definitions 6
4 Test facility 7
4.1 General 7
4.2 Test room 7
4.3 Materials 9
4.4 Test apparatus 9
4.5 Smoke exhaust system 11
4.6 General measurement section equipment 11
4.7 Other general equipment 12
5 Test specimen 13
5.1 Dimensions of specimen 13
5.2 Mounting of specimen 13
5.2.1 Mounting as in end use application 13
5.2.2 Standard mounting 13
5.3 Installation of the specimen wings in the trolley 16
5.4 Number of specimens 16
6 Conditioning 16
7 Principle 17
8 Test procedure 17
8.1 General 17
8.2 Testing operations 17
8.3 Visual observation and manual recording of data 18
8.3.1 General 18
8.3.2 Pre-test conditions 18
8.3.3 Lateral flame spread on the long wing 18
8.3.4 Flaming particles or droplets 18
8.3.5 End of test conditions 20
8.3.6 Recorded events 20
8.4 Automated recording of data 20
8.5 Early termination of test 21
9 Expression of results 21
10 Test report 21
Annex A (normative) Calculation procedures 23
A.1 General 23
A.1.1 General remarks 23
A.1.2 Calculations to be performed on the test data 23
A.1.3 Calculations to be performed on calibration data 24
A.1.4 Standard data set 24
A.2 Synchronization of data 24
A.2.1 O and CO synchronization with T 24
2 2 ms
A.3 Checking equipment response 26
A.3.1 Burner switch response time 26
A.3.2 Temperature readings 28
A.3.3 Drift in gas concentration measurement 28
A.3.4 Drift in light attenuation measurement 28
A.4 Exposure period 29
A.5 Heat output 29
A.5.1 Calculation of heat release rate (HRR)29
A.5.2 Calculation of THR(t) and THR 32
600s
A.5.3 Calculation of FIGRA and FIGRA (fire growth rate indices) 33
0,2MJ 0,4MJ
A.6 Smoke production 34
A.6.1 Calculation of smoke production rate (SPR)34
A.6.2 Calculation of TSP(t) and TSP 36
600s
A.6.3 Calculation of SMOGRA (smoke growth rate index) 37
A.7 Calculations for calibrations 38
A.7.1 Propane heat release 38
Annex B (informative) Precision of test method 39
B.1 General remarks and results 39
B.2 Calculation of test results 40
B.3 Statistical analysis 40
B.4 Statistical results 40
Annex C (normative) Calibration procedures 44
C.1 Procedures for separate pieces of equipment 44
C.1.1 General 44
C.1.2 Oxygen analyser adjustment 44
C.1.3 Oxygen analyser output noise and drift 44
C.1.4 Carbon dioxide analyser adjustment 45
C.1.5 Check of propane mass flow controller 45
C.1.6 Light system calibration 45
C.2 System response calibrations 46
C.2.1 Burner heat output step calibration 46
C.2.2 Heptane calibration 49
C.2.3 Velocity profile factor k 51
t,v
C.2.4 Flow factor k 53
t
Annex D (informative) Calibration procedures 54
D.1 Procedures for separate pieces of equipment 54
D.1.1 General 54
D.1.2 Oxygen analyser adjustment 54
D.1.3 Carbon dioxide analyser adjustment 54
D.1.4 Check of propane mass flow controller 54
D.1.5 Optical filter check 55
D.2 Check of the thermal attack on the specimens 56
D.2.1 General 56
D.2.2 Procedure 56
Annex E (normative) Design drawings 57
Annex F (informative) Data file format 92
Annex G (informative) Record sheet 95
Foreword
This European Standard has been prepared by Technical Committee CEN/TC 127 "Fire
safety in buildings", the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication
of an identical text or by endorsement, at the latest by July 2002, and conflicting national
standards shall be withdrawn at the latest by December 2003.
This document has been prepared under a mandate given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements
of EU Directive(s).
According to the CEN/CENELEC Internal Regulations, the national standards organizations of
the following countries are bound to implement this document: Austria, Belgium, the Czech
Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg,
Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.
Introduction
The classification of the reaction to fire performance of construction products (OJ No.L241
P27-28) defines the different performance classes for building products excluding floorings
and, separately, floorings. The relevant test methods for determining the performance are
being prepared by CEN/TC127.
Safety warning
The attention of all persons concerned with managing and carrying out the tests described in
this standard is drawn to the fact that fire testing can be hazardous and that toxic and/or
harmful smoke and gases can be produced during the test.
An assessment of all potential hazards and risks to health should be made and safety
precautions should be identified and provided. Smoke and gases should be removed from the
workplace. Written safety instructions should be issued. Appropriate training should be given
to relevant personnel. Laboratory personnel should ensure that they follow written safety
instructions at all times.
Special precautions are required for the propane gas supply system.
The equipment, for example tubes, couplings, flow meters, should be approved for
propane.
The burner should be equipped with a remote-controlled ignition device, for example a
pilot flame or a glow wire. There should be a warning system for leaking gas and a valve
for immediate and automatic cut-off of the gas supply in case of extinction of the ignition
flame. The pilot flames can be ignited directly by an operator in the test room, however,
no one should be present in the test room during ignition of a burner.
It should be possible to operate the switch between auxiliary and main burner and the
preceding main valve (to open or stop the propane supply) from outside the test room.
Special precautions are required for the extinction of burning specimens.
When the extinction is carried out because of intensive combustion of the specimens, it is
recommended that a second operator is ready to intervene. Means for extinguishing should
be available (e.g. since the heat output during intensive combustion can damage the
apparatus).
1 Scope
This European Standard specifies a method of test for determining the reaction to fire
performance of construction products excluding floorings, and excluding products which are
indicated in the EC Decision 2000/147/EC, when exposed to thermal attack by a single
burning item (SBI). The calculation procedures are given in annex A. Information on the
precision of the test method is given in annex B. The calibration procedures are given in
annexes C and D, of which C is a normative annex.
NOTE This European Standard has been developed to determine the reaction to fire performance
of essentially flat products. The treatment of some families of products, e.g. linear products (pipes,
ducts, cables etc) can need special rules.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text, and
the publications are listed hereafter. For dated references, subsequent amendments to or
revisions of any of these publications apply to this European Standard only when incorporated
in it by amendment or revision. For undated references the latest edition of the publication
referred to applies (including amendments).
EN 60584-1, Thermocouples – Part 1: Reference tables (IEC 584-1:1995).
EN 13501-1, Fire classification of construction products and building elements – Part 1:
Classification using test data from reaction to fire tests.
EN 13238, Reaction to fire tests for building products - Conditioning procedures and general
rules for selection of substrates.
EN ISO 13943, Fire safety – Vocabulary (ISO 13943:2000).
3 Terms and definitions
For the purposes of this European Standard, the terms and definitions in EN ISO 13943 and
EN 13501-1 apply, together with the following.
3.1
backing board
calcium silicate panel used to back the specimen that can be placed directly against a free-
standing test specimen or at a distance from it
3.2
specimen
piece of a product, which is to be tested
NOTE This can include the mounting technique used in its end-use application. This also can
include an air gap and/or a substrate where appropriate.
3.3
substrate
product which is used immediately beneath the product about which information is required
3.4
THR
600s
total heat release from the specimen in the first 600 s of exposure to the main burner flames
3.5
LFS
lateral flame spread on the long specimen wing
NOTE The LFS is defined in more detail in 8.3.3.
3.6
TSP
600s
total smoke production from the specimen in the first 600 s of exposure to the main burner
flames
3.7
FIGRA
0,2 MJ
maximum of the quotient of heat release rate from the specimen and the time of its
occurrence using a THR-threshold of 0,2 MJ.
NOTE The FIGRA is described in more detail in A.5.3.
0,2 MJ
3.8
FIGRA
0,4 MJ
maximum of the quotient of heat release rate from the specimen and the time of its
occurrence using a THR threshold of 0,4 MJ.
NOTE The FIGRA is described in more detail in A.5.3
0,4 MJ
3.9
SMOGRA
smoke growth rate. The maximum of the quotient of smoke production rate from the specimen
and the time of its occurrence
NOTE The SMOGRA is described in more detail in A.6.3.
3.10
sustained flaming
persistence of flame on or over a surface for a minimum period of time
[EN ISO 13943]
4 Test facility
4.1 General
The SBI test facility shall consist of a test room, the test apparatus (trolley, frame, burners,
hood, collector and ducting), the smoke exhaust system and general measuring equipment.
These components are specified in 4.2 to 4.7. Design drawings are given in annex E.
Dimensions given in the drawings are nominal unless tolerances are given in the text.
NOTE The air supply to the test room entering below the trolley should be fresh, uncontaminated
air.
4.2 Test room
4.2.1 The test room shall have an inner height of (2,4 0,1) m and an inner floor area of
(3,0 0,2) m in both directions. The walls shall be made of stone type building blocks (e.g.
cellular concrete), gypsum boards, calcium silicate boards or other boards classified as
Euroclass A1 or A2.
4.2.2 One wall of the test room shall have an opening to insert the trolley from the
surrounding laboratory into the test room. The opening shall be at least 1 470 mm wide and
2 450 mm high (dimensions of the frame). Windows shall be placed in the two walls facing the
front side of the two perpendicular specimen planes. To be able to handle the SBI apparatus
and the specimen when the trolley is in place, an additional door is needed.
4.2.3 With the trolley in place in the test room, the distance between the long wing
specimen surface touching the U-profile and the wall of the test room shall be (2,1 0,1) m.
This distance shall be measured perpendicularly to the wall facing the long wing. The areas of
the openings in the test room, excluding the air inlet at the bottom of the trolley and the smoke
exhaust opening in the hood, shall not exceed a total of 0,05 m .
4.2.4 Both left-orientated arrangements, as shown in Figure 1, and right-orientated
arrangements (the trolley shown in Figure 1 mirrored around a vertical line) are allowed.
NOTE 1 To be able to remove side plates of the hood without removing the collector, attention should
be paid to the co
...