Water conditioning equipment inside buildings - Mechanical filters - Part 1: Particle rating 80 µm to 150 µm - Requirements for performances, safety and testing

Part 1 of this European standard applies to mechanical filters for drinking water installations inside buildings, of nominal size from DN 15 to DN 100, minimum nominal pressure PN10, particle rating of 80 to 150 µm, and minimum design temperature of 30°C. It specifies requirements relating to the construction and mode of operation of filters and describes relevant methods of testing. It only concerns units which are permanently connected to the mains supply at the point of entry into the building.

Anlagen zur Behandlung von Trinkwasser innerhalb von Gebäuden - Mechanisch wirkende Filter - Teil 1: Filterfeinheit 80 µm bis 150 µm - Anforderungen an Ausführung und Sicherheit, Prüfung

Teil 1 dieser Europäischen Norm gilt für mechanisch wirkende Filter in der Trinkwasser-Installation innerhalb von Gebäuden mit einer Nennweite von DN 15 bis DN 100, einem minimalen Nenndruck von PN10, einer Durchlassweite 80 µm bis 150 µm und einer minimalen Auslegungstemperatur von 30 °C. Die Norm spezifiziert Anforderungen in Bezug auf Konstruktion und Funktion von Filtergeräten und beschreibt relevante Prüfverfahren. Sie bezieht sich nur auf fest installierte Geräte am Eintrittspunkt der Anschlussleitung in die Hausinstallation.
Teil 2 dieser Europäischen Norm (prEN 13443-2) ist ein weiteres Dokument und gilt für Filtergeräte mit einer Filterfeinheit geringer als 80 µm.

Appareils de conditionnement d'eau a l'intérieur des bâtiments - Filtres mécaniques - Partie 1: Particules de dimension comprise entre 80 µm et 150 µm - Exigences de performances et de sécurité, essais

La première partie de la présente Norme européenne s'applique aux filtres mécaniques utilisés dans les installations d'eau potable à l'intérieur des bâtiments, de diamètre nominal compris entre DN 15 et DN 100, de pression nominale PN 10, de seuil de filtration des particules compris entre 80  m et 150  m et de température opérationnelle minimale de 30 °C. Elle spécifie les exigences relatives à la fabrication et au mode de fonctionnement des filtres et décrit les méthodes d'essais adaptées. Elle ne concerne que les éléments raccordés en permanence au point d'entrée du réseau de distribution d'eau dans le bâtiment.
La seconde partie de la présente norme (prEN 13443-2) est un document séparé qui traite des filtres dont le seuil de filtration est limité aux particules de taille inférieure à 80  m.

Oprema, ki se uporablja za pripravo pitne vode v stavbah – Mehanski filtri – 1. del: Filtri za izločitev delcev z velikostjo 80 µm do 150 µm - Zahteve za delovanje, varnost in preskušanje

General Information

Status
Withdrawn
Publication Date
30-Sep-2003
Withdrawal Date
06-Mar-2016
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
04-Mar-2016
Due Date
27-Mar-2016
Completion Date
07-Mar-2016

Relations

Buy Standard

Standard
EN 13443-1:2003
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Anlagen zur Behandlung von Trinkwasser innerhalb von Gebäuden - Mechanisch wirkende Filter - Teil 1: Filterfeinheit 80 µm bis 150 µm - Anforderungen an Ausführung und Sicherheit, PrüfungAppareils de conditionnement d'eau a l'intérieur des bâtiments - Filtres mécaniques - Partie 1: Particules de dimension comprise entre 80 µm et 150 µm - Exigences de performances et de sécurité, essaisWater conditioning equipment inside buildings - Mechanical filters - Part 1: Particle rating 80 µm to 150 µm - Requirements for performances, safety and testing91.140.60Sistemi za oskrbo z vodoWater supply systems13.060.20Pitna vodaDrinking waterICS:Ta slovenski standard je istoveten z:EN 13443-1:2002SIST EN 13443-1:2003en01-oktober-2003SIST EN 13443-1:2003SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 13443-1December 2002ICS 13.060.20; 91.140.60English versionWater conditioning equipment inside buildings - Mechanicalfilters - Part 1: Particle rating 80 µm to 150 µm - Requirementsfor performances, safety and testingAppareils de conditionnement d'eau à l'intérieur desbâtiments - Filtres mécaniques - Partie 1: Particules dedimension comprise entre 80 µm et 150 µm - Spécificationsde performances et de sécurité, essaisAnlagen zur Behandlung von Trinkwasser innerhalb vonGebäuden - Mechanisch wirkende Filter - Teil 1:Filterfeinheit 80 µm bis 150 µm - Anforderungen anAusführung und Sicherheit, PrüfungThis European Standard was approved by CEN on 23 October 2002.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2002 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 13443-1:2002 ESIST EN 13443-1:2003

Bibliographical information.19Bibliography.22SIST EN 13443-1:2003

pressure drop does not exceed a value of 50 kPa (0,5 bar), or the filtersurface velocity does not exceed the maximum specified value, whichever is lower4 Classification4.1 PrincipleMechanical filters shall be designated by:¾ nominal size DN;¾ end connections;¾ filter type;¾ nominal pressure PN.The designation shall be clearly identified on the manufacturer's rating plate or in the instruction manual. Examplesare given in annex A.4.2 Nominal size (DN)The nominal size DN shall correspond to the flow rates in Table 2. The inlet connection of the filter may be DN orone size larger or one size smaller than the nominal size DN. In the case of flange connections the nominal sizeDN is determined by the DN of the inlet connection.4.3 End ConnectionsExamples of end connections are shown in annex A. Combinations of two kinds of connections are possible.4.4 Filter TypeFilters conforming to this standard shall be presented as one of the following types:¾ filters requiring single use filter elements;SIST EN 13443-1:2003
...