SIST EN 1264-4:2002
(Main)Floor heating - Systems and components - Part 4: Installation
Floor heating - Systems and components - Part 4: Installation
This European Standard is applicable to hot water floor heating systems as defined in EN 1264-1:1997.
This European Standard specifies uniform requirements for the design and the construction of heated floor structures to ensure that the underfloor heating system is suited to the particular application.
This European Standard specifies only the particular requirements which are dependent on the floor heating. This European Standard is not applicable to the other elements which are part of all floor structures (heated or not).
Fußboden-Heizung - Systeme und Komponenten - Teil 4: Installation
Diese Europäische Norm gilt für Warmwasser-Fußbodenheizungen, die EN 1264-1:1997 definiert sind. Diese Europäische Norm legt einheitliche Anforderungen an den Aufbau einer beheizten Fußbodenkonstruktion fest, um sicherzustellen, dass die Fußbodenheizung für den jeweiligen Verwendungszweck geeignet ist. Diese Europäische Norm legt nur die besonderen Anforderungen fest, die für die Fußbodenheizung entscheidend sind. Diese Europäische Norm gilt nicht für die weiteren Elemente, die Bestandteil sämtlicher Fußbodenkonstruktionen (beheizt oder unbeheizt) sind.
Chauffage par le sol - Systemes et composants - Partie 4: Installation
La présente Norme européenne est applicable aux systèmes de chauffage par le sol à eau chaude tels qu'ils sont définis dans l'EN 1264-1:1997.
La présente Norme européenne spécifie les exigences de conception et de mise en ¿uvre des planchers chauffants pour s'assurer que les systèmes de chauffage par le sol sont adaptés à cette application particulière.
La présente Norme européenne traite uniquement des exigences particulières liées au chauffage par le sol. Les autres éléments qui ont rapport avec tous les planchers (chauffés ou non) doivent satisfaire aux autres normes applicables.
Talno ogrevanje - Sistemi in sestavni deli - 4. del: Vgradnja
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Talno ogrevanje - Sistemi in sestavni deli - 4. del: VgradnjaFußboden-Heizung - Systeme und Komponenten - Teil 4: InstallationChauffage par le sol - Systemes et composants - Partie 4: InstallationFloor heating - Systems and components - Part 4: Installation91.140.10Sistemi centralnega ogrevanjaCentral heating systemsICS:Ta slovenski standard je istoveten z:EN 1264-4:2001SIST EN 1264-4:2002en01-april-2002SIST EN 1264-4:2002SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 1264-4August 2001ICS 91.140.10English versionFloor heating - Systems and components - Part 4: InstallationChauffage par le sol - Systèmes et composants - Partie 4:InstallationFußboden-Heizung - Systeme und Komponenten - Teil 4:InstallationThis European Standard was approved by CEN on 4 July 2001.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2001 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 1264-4:2001 ESIST EN 1264-4:2002
Oxygen barrier layer.11SIST EN 1264-4:2002
the thermal output-Part 3 : Dimensioning-Part 4 : Installation1ScopeThis European Standard is applicable to hot water floor heating systems as defined in EN 1264-1:1997.This European Standard specifies uniform requirements for the design and the construction of heated floorstructures to ensure that the underfloor heating system is suited to the particular application.This European Standard specifies only the particular requirements which are dependent on the floorheating. This European Standard is not applicable to the other elements which are part of all floorstructures (heated or not).2 Normative referencesThis European Standard incorporates by dated or undated reference, provisions from other publications.These normative references are cited at the appropriate place in the text, and the publications are listedhereafter. For dated references, subsequent amendments to or revisions of any of these publications applyto this European Standard only when incorporated in it by amendment or revision. For undated references,the latest edition of the publication referred to applies (including amendments).EN 1057:1996Copper and copper alloys - Seamless, round copper tubes for water and gasin sanitary and heating applications.EN 1254Plumbing fittings.EN 1264-1:1997Floor heating – Systems and components - Part 1: Definitions and Symbols.prEN ISO 15874-1:2001Plastics piping systems for hot and cold water - Polypropylene (PP) – Part 1:General.prEN ISO 15875-1:2001Plastics piping systems for hot and cold water - Crosslinked polyethylene(PEX) - Part 1: General.prEN ISO 15876-1:2001Plastics piping systems for hot and cold water - Polybutylene (PB) - Part 1:General.3Terms, definitions and symbolsFor the purposes of this European Standard, the terms, definitions and symbols given in EN 1264-1:1997apply.4 Requirements4.1General structural preconditionsPreconditions for the construction of a hot water floor heating system are the completion of internalplasterwork and the draught-free closure of all building openings e.g. windows and outer doors.SIST EN 1264-4:2002
0°Cexternal designtemperature0°C > Td
-5°Cexternal designtemperature-5°C > Td
-15°Cthermalresistance(m2 K/W)0,751,251,251,502,00*) with ground water level
5m, the value should be increased.When installing the insulating layer, the insulating panels shall be butted tightly together. Multiple insulatinglayers shall be staggered or placed in such a way that the joints between panels of one layer are out of linewith the next layer.4.2.2.2Perimeter stripPrior to the laying of the screed, a perimeter expansion strip (edge joint) shall be placed along the wallsand other building components penetrating the screed and firmly secured to the supporting base, e.g. doorframes, pillars and risers.The perimeter strip shall rise from the supporting base up to the surface of the finished floor and permit amovement of the screed of at least 5 mm.In the case of multiple insulating layers, the perimeter strip shall be placed prior to application of the upperinsulating layer. When laying the screed, the peripheral insulating strip shall be secured against anychange in position. The top part of the peripheral insulating strip which rise over the finished floor shall notbe cut off until completion of the floor covering and, in the case of textile and plastic coverings, hardeningof the filler.4.2.3Protection layerPrior to laying the screed, the insulation layer shall be covered with a polyethylene film of at least 0,15 mmthickness or with another product equivalent function unless the insulating layer is a comparable protectivecomposit. The individual sections shall overlap at the joints by at least 80 mm.SIST EN 1264-4:2002
4 bar;-Life time
50 years.2)A separate requirement for the minimum wall thickness is :D
12 mmsR,min = 1,1 mm12 mm < D
16 mmsR,min = 1,5 mmD > 16 mmsR,min = 1,9 mmThe above dimensions are valid for the basic-pipes in conformity with prEN ISO 15875:2001, prEN ISO15876:2001 and prEN ISO 15874:2001 without barrier layers.SIST EN 1264-4:2002
More frequent attachments provide greater security concerning pipe positioning. Spacing of the attachmentsdepends on the system applied. Experience has shown that systems with individual attachments necessitate spacingsof approximately 500 mm in order to comply with the above mentioned requirements.4.2.8Screeds (Load distribution layer)4.2.8.1Types of screedsFor heating screeds, the following types are distinguished (see EN 1264-1:1997, 3.11):-Type A - Systems with pipes inside screed-Type B - System with pipes under the screedSIST E
...