Fire protection — Automatic sprinkler systems — Part 1: Requirements and test methods for sprinklers

This document specifies performance and marking requirements and test methods for conventional, spray, flat spray, sidewall, extended coverage, domestic and storage sprinklers, including early suppression fast response (ESFR), electrically activated sprinklers (EAS) and sprinklers with monitoring of activation (SMA) for use in water-based fire protection systems. This document is not applicable to sprinklers with multiple orifices.

Protection contre l'incendie — Systèmes d'extinction automatiques du type sprinkler — Partie 1: Prescriptions et méthodes d'essai des sprinklers

General Information

Status
Published
Publication Date
24-May-2021
Current Stage
6060 - International Standard published
Start Date
25-May-2021
Due Date
27-Aug-2022
Completion Date
25-May-2021
Ref Project

Relations

Standard
ISO 6182-1:2021:Version 05-jun-2021 - Fire protection -- Automatic sprinkler systems
English language
125 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 6182-1:2021 - Fire protection -- Automatic sprinkler systems
English language
125 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


INTERNATIONAL ISO
STANDARD 6182-1
Fourth edition
2021-05
Fire protection — Automatic sprinkler
systems —
Part 1:
Requirements and test methods for
sprinklers
Protection contre l'incendie — Systèmes d'extinction automatiques du
type sprinkler —
Partie 1: Prescriptions et méthodes d'essai des sprinklers
Reference number
©
ISO 2021
© ISO 2021
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting
on the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address
below or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii © ISO 2021 – All rights reserved

Contents Page
Foreword .vii
Introduction .viii
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
3.1 General . 1
3.2 Types of sprinklers according to type of responsive element . 4
3.3 Types of sprinklers according to type of water distribution . 4
3.4 Types of sprinklers according to position . 5
3.5 Special types of sprinklers . 6
3.6 Types of sprinklers according to sprinkler sensitivity . 7
4 Product consistency . 8
4.1 Quality control programme . 8
4.2 Leak resistance testing . 8
4.3 Glass bulb integrity test . 8
5 Product assembly. 8
5.1 General . 8
5.2 Dynamic O-ring seals . 8
5.3 Rated pressure . 8
5.4 Dry sprinklers . 9
5.5 Escutcheons . 9
6 Requirements . 9
6.1 General . 9
6.1.1 Electrically activated sprinkler and monitoring of activation . 9
6.1.2 Orifice size . 9
6.1.3 Nominal thread sizes . 9
6.2 Maximum coverage areas and spacing .10
6.3 Temperature ratings and colour coding .10
6.4 Service load and strength of sprinkler body (see 7.4) .11
6.5 Strength of heat-responsive element (see 7.5) .11
6.5.1 Glass bulb elements . .11
6.5.2 Fusible elements .12
6.6 Leak resistance and hydrostatic strength (see 7.6) .12
6.7 Thirty-day leakage resistance (see 7.7) .12
6.8 Vacuum resistance (see 7.8) .13
6.9 Water hammer (see 7.9) .13
6.10 Vibration (see 7.10) .13
6.11 Deflector strength (see 7.11) .13
6.12 Water shield rotation (see 7.12) .13
6.13 Impact (see 7.13) .13
6.14 Protective covers (see 7.14) .13
6.15 Rough usage (see 7.15) .14
6.16 Dry sprinkler air tightness (see 7.16) .14
6.17 Operating temperature (see 7.17) .14
6.18 Sensitivity — response time index (RTI) (see 7.18) .14
6.18.1 Pre-exposure RTI .14
6.18.2 Post-exposure RTI . .15
6.19 Sensitivity test of flush, concealed and recessed sprinklers (see 7.19) .15
6.19.1 General.15
6.19.2 Room response test (see 7.19.2) .15
6.19.3 Plunge test (see 7.19.3) .15
6.20 Lodgement (see 7.20) .16
6.21 Heat exposure (see 7.21) .17
6.21.1 Glass bulb sprinklers .17
6.21.2 All sprinklers .17
6.21.3 Coated sprinklers .17
6.22 Sprinkler coatings (see 7.22) .17
6.22.1 Evaporation of wax and bitumen .17
6.22.2 Resistance to low temperatures .17
6.23 Thermal shock for glass bulb sprinklers (see 7.23) .17
6.24 Resistance to heat (see 7.24) .17
6.25 Freezing test (see 7.25) .17
6.26 Corrosion (see 7.26) .18
6.26.1 Stress corrosion for copper-based alloy components (see 7.26.1) .18
6.26.2 Stress corrosion for stainless steel components (see 7.26.2) .18
6.26.3 Sulphur dioxide/carbon dioxide corrosion (see 7.26.3) .18
6.26.4 Hydrogen sulphide corrosion (see 7.26.4) .18
6.26.5 Salt spray loading (see 7.26.5) .18
6.26.6 Moist air exposure (see 7.26.6) .19
6.26.7 Dry-type sprinkler deposit loading (see 7.26.7) .19
6.26.8 Dezincification of brass parts (see 7.26.8) .19
6.27 Water flow constant (see 7.27) .19
6.28 Water distribution (see 7.28) .20
6.28.1 General.20
6.28.2 Spray, flat spray, conventional and dry sprinkler water distribution (see
7.28.2) .21
6.28.3 Domestic sprinkler water distribution (see 7.28.3) .
...


INTERNATIONAL ISO
STANDARD 6182-1
Fourth edition
2021-05
Corrected version
2021-08
Fire protection — Automatic sprinkler
systems —
Part 1:
Requirements and test methods for
sprinklers
Protection contre l'incendie — Systèmes d'extinction automatiques du
type sprinkler —
Partie 1: Prescriptions et méthodes d'essai des sprinklers
Reference number
©
ISO 2021
© ISO 2021
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting
on the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address
below or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii © ISO 2021 – All rights reserved

Contents Page
Foreword .vii
Introduction .ix
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
3.1 General . 1
3.2 Types of sprinklers according to type of responsive element . 4
3.3 Types of sprinklers according to type of water distribution . 4
3.4 Types of sprinklers according to position . 5
3.5 Special types of sprinklers . 6
3.6 Types of sprinklers according to sprinkler sensitivity . 7
4 Product consistency . 8
4.1 Quality control programme . 8
4.2 Leak resistance testing . 8
4.3 Glass bulb integrity test . 8
5 Product assembly. 8
5.1 General . 8
5.2 Dynamic O-ring seals . 8
5.3 Rated pressure . 8
5.4 Dry sprinklers . 9
5.5 Escutcheons . 9
6 Requirements . 9
6.1 General . 9
6.1.1 Electrically activated sprinkler and monitoring of activation . 9
6.1.2 Orifice size . 9
6.1.3 Nominal thread sizes . 9
6.2 Maximum coverage areas and spacing .10
6.3 Temperature ratings and colour coding .10
6.4 Service load and strength of sprinkler body (see 7.4) .11
6.5 Strength of heat-responsive element (see 7.5) .11
6.5.1 Glass bulb elements . .11
6.5.2 Fusible elements .12
6.6 Leak resistance and hydrostatic strength (see 7.6) .12
6.7 Thirty-day leakage resistance (see 7.7) .12
6.8 Vacuum resistance (see 7.8) .13
6.9 Water hammer (see 7.9) .13
6.10 Vibration (see 7.10) .13
6.11 Deflector strength (see 7.11) .13
6.12 Water shield rotation (see 7.12) .13
6.13 Impact (see 7.13) .13
6.14 Protective covers (see 7.14) .13
6.15 Rough usage (see 7.15) .14
6.16 Dry sprinkler air tightness (see 7.16) .14
6.17 Operating temperature (see 7.17) .14
6.18 Sensitivity — response time index (RTI) (see 7.18) .14
6.18.1 Pre-exposure RTI .14
6.18.2 Post-exposure RTI . .15
6.19 Sensitivity test of flush, concealed and recessed sprinklers (see 7.19) .15
6.19.1 General.15
6.19.2 Room response test (see 7.19.2) .15
6.19.3 Plunge test (see 7.19.3) .15
6.20 Lodgement (see 7.20) .16
6.21 Heat exposure (see 7.21) .17
6.21.1 Glass bulb sprinklers .17
6.21.2 All sprinklers .17
6.21.3 Coated sprinklers .17
6.22 Sprinkler coatings (see 7.22) .17
6.22.1 Evaporation of wax and bitumen .17
6.22.2 Resistance to low temperatures .17
6.23 Thermal shock for glass bulb sprinklers (see 7.23) .17
6.24 Resistance to heat (see 7.24) .17
6.25 Freezing test (see 7.25) .17
6.26 Corrosion (see 7.26) .18
6.26.1 Stress corrosion for copper-based alloy components (see 7.26.1) .18
6.26.2 Stress corrosion for stainless steel components (see 7.26.2) .18
6.26.3 Sulphur dioxide/carbon dioxide corrosion (see 7.26.3) .18
6.26.4 Hydrogen sulphide corrosion (see 7.26.4) .18
6.26.5 Salt spray loading (see 7.26.5) .18
6.26.6 Moist air exposure (see 7.26.6) .19
6.26.7 Dry-type sprinkler deposit loading (see 7.26.7) .19
6.26.8 Dezincification of brass parts (see 7.26.8) .19
6.27 Water flow constant (see 7.27) .19
6.28 Water distribution (see 7.28) .20
6.28.1 General.20
6.28.2 Spray, flat spray, conventional and dry sprinkler water distribution (see
7.28.2) .21
6.28.3 Domestic sprinkler water distribution (see 7.28.3) .
...

Questions, Comments and Discussion