ASTM F1802-15
(Test Method)Standard Test Method for Performance Testing of Excess Flow Valves
Standard Test Method for Performance Testing of Excess Flow Valves
SIGNIFICANCE AND USE
5.1 This test method is intended to be used for the evaluation of EFVs manufactured for use on residential and small commercial thermoplastic natural gas service lines. Possible applications of the test include product design and quality control testing by a manufacturer and product acceptance testing by a natural gas utility.
5.2 The user of this test method should be aware that the flows and pressures measured in the test apparatus may not correlate well with those measured in a field installation. Therefore, the user should conduct sufficient tests to ensure that any specific EFV will carry out its intended function in the actual field installation used.
SCOPE
1.1 This test method covers a standardized method to determine the performance of excess flow valves (EFVs) designed to limit flow or stop flow in thermoplastic natural gas service lines.2
1.2 All tests are intended to be performed using air as the test fluid. Unless otherwise stated, all flow rates are reported in standard cubic feet per hour of 0.6 relative density natural gas.
1.3 The test method recognizes two types of EFV. One type, an excess flow valve-bypass (EFVB), allows a small amount of gas to bleed through (bypass) after it has tripped, usually as a means of automatically resetting the device. The second type, an excess flow valve-non bypass (EFVNB), is intended to trip shut forming an essentially gas tight seal.
1.4 The performance characteristics covered in this test method include flow at trip point, pressure drop across the EFV, bypass flow rate of the EFVB or leak rate through the EFVNB after trip, and verification that the EFV can be reset.
1.4.1 Gas distribution systems may contain condensates and particulates such as organic matter, sand, dirt, and iron compounds. Field experience has shown that the operating characteristics of some EFVs may be affected by accumulations of these materials. The tests of Section 11 were developed to provide a simple, inexpensive, reproducible test that quantifies the effect, if any, of a uniform coating of kerosene and of kerosene contaminated with a specified amount of ferric oxide powder on an EFV's operating characteristics.
1.5 Excess flow valves covered by this test method will normally have the following characteristics: a pressure rating of up to 125 psig (0.86 MPa); a trip flow of between 200 and 2500 ft3/h (5.66 and 70.8 m3/h) at 10 psig (0.07 MPa); a minimum temperature rating of 0°F(–18°C), and a maximum temperature rating of 100°F (38°C).
1.6 The EFVs covered by this test method shall be constructed to fit piping systems no smaller than 1/2 CTS and no larger than 11/4 IPS, including both pipe and tubing sizes.
1.7 Tests will be performed at 67 ± 10°F (19.4 ± 5.5°C). Alternative optional test temperatures are 100 ± 10°F (37.7 ± 5.5°C) and 0 ± 10°F (–18 ± 5.5°C). All flow rates must be corrected to standard conditions.
1.8 This test method was written for EFVs installed in thermoplastic piping systems. However, it is expected that the test method may also be used for similar devices in other piping systems.
1.9 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautions, see Section 8.
General Information
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F1802 − 15
Standard Test Method for
1
Performance Testing of Excess Flow Valves
This standard is issued under the fixed designation F1802; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
3 3
1. Scope 2500 ft /h (5.66 and 70.8 m /h) at 10 psig (0.07 MPa); a
minimum temperature rating of 0°F(–18°C), and a maximum
1.1 This test method covers a standardized method to
temperature rating of 100°F (38°C).
determine the performance of excess flow valves (EFVs)
designed to limit flow or stop flow in thermoplastic natural gas 1.6 The EFVs covered by this test method shall be con-
2
1
service lines. structed to fit piping systems no smaller than ⁄2 CTS and no
1
larger than 1 ⁄4 IPS, including both pipe and tubing sizes.
1.2 All tests are intended to be performed using air as the
test fluid. Unless otherwise stated, all flow rates are reported in 1.7 Tests will be performed at 67 6 10°F (19.4 6 5.5°C).
standard cubic feet per hour of 0.6 relative density natural gas. Alternative optional test temperatures are 100 6 10°F (37.7 6
5.5°C) and 0 6 10°F (–18 6 5.5°C). All flow rates must be
1.3 The test method recognizes two types of EFV. One type,
corrected to standard conditions.
anexcessflowvalve-bypass(EFVB),allowsasmallamountof
gas to bleed through (bypass) after it has tripped, usually as a 1.8 This test method was written for EFVs installed in
means of automatically resetting the device. The second type, thermoplastic piping systems. However, it is expected that the
an excess flow valve-non bypass (EFVNB), is intended to trip test method may also be used for similar devices in other
shut forming an essentially gas tight seal. piping systems.
1.4 The performance characteristics covered in this test 1.9 The values stated in inch-pound units are to be regarded
method include flow at trip point, pressure drop across the as standard. The values given in parentheses are mathematical
EFV, bypass flow rate of the EFVB or leak rate through the conversions to SI units that are provided for information only
EFVNB after trip, and verification that the EFV can be reset. and are not considered standard.
1.4.1 Gas distribution systems may contain condensates and
1.10 This standard does not purport to address all of the
particulates such as organic matter, sand, dirt, and iron com-
safety concerns, if any, associated with its use. It is the
pounds. Field experience has shown that the operating charac-
responsibility of the user of this standard to establish appro-
teristics of some EFVs may be affected by accumulations of
priate safety and health practices and determine the applica-
these materials. The tests of Section 11 were developed to
bility of regulatory limitations prior to use. For specific
provide a simple, inexpensive, reproducible test that quantifies
precautions, see Section 8.
the effect, if any, of a uniform coating of kerosene and of
kerosene contaminated with a specified amount of ferric oxide
2. Referenced Documents
powder on an EFV’s operating characteristics.
3
2.1 ASTM Standards:
1.5 Excess flow valves covered by this test method will
D1600 TerminologyforAbbreviatedTermsRelatingtoPlas-
normally have the following characteristics: a pressure rating
tics
of up to 125 psig (0.86 MPa); a trip flow of between 200 and
E177 Practice for Use of the Terms Precision and Bias in
ASTM Test Methods
E691 Practice for Conducting an Interlaboratory Study to
1
Determine the Precision of a Test Method
This test method is under the jurisdiction of ASTM Committee F17 on Plastic
Piping Systems and is the direct responsibility of Subcommittee F17.40 on Test
F412 Terminology Relating to Plastic Piping Systems
Methods.
2.2 ANSI Standard:
Current edition approved Nov. 1, 2015. Published May 2016. Originally
4
B31.8 Gas Transmission and Distribution Piping Systems
approved in 1995 as PS 13–95. Last previous edition approved in 2010 as
F1802–04(2010). DOI: 10.1520/F1802-15.
2
This contamination test procedure may be utilized to determine the effect, if
3
any, of contaminants from a specific gas distribution system on the operational For referenced ASTM standards, visit the ASTM website, www.astm.org, or
characteristics of an EFV under consideration for use in that system. Condensates, contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
oils and particulates removed from that distribution system could be substituted for Standards volume information, refer to the standard’s Document Summary page on
keroseneandironoxide.Resultsobtainedfromusingreagentsorcontaminantsother the ASTM website.
4
than those specified in th
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F1802 − 04 (Reapproved 2010) F1802 − 15
Standard Test Method for
1
Performance Testing of Excess Flow Valves
This standard is issued under the fixed designation F1802; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method covers a standardized method to determine the performance of excess flow valves (EFVs) designed to limit
2
flow or stop flow in thermoplastic natural gas service lines.
1.2 All tests are intended to be performed using air as the test fluid. Unless otherwise stated, all flow rates are reported in
standard cubic feet per hour of 0.6 relative density natural gas.
1.3 The test method recognizes two types of EFV. One type, an excess flow valve-bypass (EFVB), allows a small amount of
gas to bleed through (bypass) after it has tripped, usually as a means of automatically resetting the device. The second type, an
excess flow valve-non bypass (EFVNB), is intended to trip shut forming an essentially gas tight seal.
1.4 The performance characteristics covered in this test method include flow at trip point, pressure drop across the EFV, bypass
flow rate of the EFVB or leak rate through the EFVNB after trip, and verification that the EFV can be reset.
1.4.1 Gas distribution systems may contain condensates and particulates such as organic matter, sand, dirt, and iron compounds.
Field experience has shown that the operating characteristics of some EFVs may be affected by accumulations of these materials.
The tests of Section 11 were developed to provide a simple, inexpensive, reproducible test that quantifies the effect, if any, of a
uniform coating of kerosene and of kerosene contaminated with a specified amount of ferric oxide powder on an EFV’s operating
characteristics.
1.5 Excess flow valves covered by this test method will normally have the following characteristics: a pressure rating of up to
3 3
125 psig (0.86 MPa); a trip flow of between 200 and 2500 ft /h (5.66 and 70.8 m /h) at 10 psig (0.07 MPa); a minimum temperature
rating of 0°F(–18°C), and a maximum temperature rating of 100°F (38°C).
1
1.6 The EFVs covered by this test method shall be constructed to fit piping systems no smaller than ⁄2 CTS and no larger than
1
1 ⁄4 IPS, including both pipe and tubing sizes.
1.7 Tests will be performed at 67 6 10°F (19.4 6 5.5°C). Alternative optional test temperatures are 100 6 10°F (37.7 6 5.5°C)
and 0 6 10°F (–18 6 5.5°C). All flow rates must be corrected to standard conditions.
1.8 This test method was written for EFVs installed in thermoplastic piping systems. However, it is expected that the test
method may also be used for similar devices in other piping systems.
1.9 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use. For specific precautions, see Section 8.
2. Referenced Documents
3
2.1 ASTM Standards:
D1600 Terminology for Abbreviated Terms Relating to Plastics
1
This test method is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.40 on Test Methods.
Current edition approved Aug. 1, 2010Nov. 1, 2015. Published November 2010May 2016. Originally approved in 1995 as PS 13–95. Last previous edition approved in
20042010 as F1804F1802–04(2010).–04. DOI: 10.1520/F1802-04R10.10.1520/F1802-15.
2
This contamination test procedure may be utilized to determine the effect, if any, of contaminants from a specific gas distribution system on the operational characteristics
of an EFV under consideration for use in that system. Condensates, oils and particulates removed from that distribution system could be substituted for kerosene and iron
oxide. Results obtained from using reagents or contaminants other than those specified in this test method must not be used in comparison with results obtained using the
reagents specified in this test method.
3
For referenced ASTM standards, visit the ASTM webs
...










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.