Standard Test Method for Measurement of Smoke Obscuration Using a Conical Radiant Source in a Single Closed Chamber, With the Test Specimen Oriented Horizontally

SCOPE
1.1 This is a fire-test-response standard.
1.2 This test method provides a means of measuring smoke obscuration resulting from subjecting essentially flat materials, products, or assemblies (including surface finishes), not exceeding 25 mm [1 in.] in thickness, in a horizontal orientation, exposed to specified levels of thermal irradiance, from a conical heater, in the presence of a pilot flame, in a single closed chamber. Optional testing modes exclude the pilot flame.
1.3 The principal fire-test-response characteristic obtained from this test method is the specific optical density of smoke from the specimens tested, which is obtained as a function of time, for a period of 10 min.
1.4 An optional fire-test-response characteristic measurable with this test method is the mass optical density (see ), which is the specific optical density of smoke divided by the mass lost by the specimens during the test.
1.5 The fire-test-response characteristics obtained from this test are specific to the specimen tested, in the form and thickness tested, and are not an inherent property of the material, product, or assembly.
1.6 This test method does not provide information on the fire performance of the test specimens under fire conditions other than those conditions specified in this test method. For limitations of this test method, see 5.5.
1.7 Use the SI system of units in referee decisions; see IEEE/ASTM SI-10. The inch-pound units given in brackets are for information only.
1.8 This test method is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.
1.9 Fire testing of products and materials is inherently hazardous, and adequate safeguards for personnel and property shall be employed in conducting these tests. This test method may involve hazardous materials, operations, and equipment. See also 6.2.1.2, Section 7, and 11.7.2.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Mar-2004
Technical Committee
Current Stage
Ref Project

Relations

Effective Date
01-Apr-2004

Buy Standard

Standard
ASTM E1995-04a - Standard Test Method for Measurement of Smoke Obscuration Using a Conical Radiant Source in a Single Closed Chamber, With the Test Specimen Oriented Horizontally
English language
24 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
An American National Standard
Designation: E 1995 – 04a
Standard Test Method for
Measurement of Smoke Obscuration Using a Conical
Radiant Source in a Single Closed Chamber, With the Test
1
Specimen Oriented Horizontally
This standard is issued under the fixed designation E 1995; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope assessment of the materials, products, or assemblies under
actual fire conditions.
1.1 This is a fire-test-response standard.
1.9 Fire testing of products and materials is inherently
1.2 This test method provides a means of measuring smoke
hazardous, and adequate safeguards for personnel and property
obscuration resulting from subjecting essentially flat materials,
shall be employed in conducting these tests. This test method
products, or assemblies (including surface finishes), not ex-
may involve hazardous materials, operations, and equipment.
ceeding 25 mm [1 in.] in thickness, in a horizontal orientation,
See also 6.2.1.2, Section 7, and 11.7.2.
exposed to specified levels of thermal irradiance, from a
1.10 This standard does not purport to address all of the
conical heater, in the presence of a pilot flame, in a single
safety concerns, if any, associated with its use. It is the
closed chamber. Optional testing modes exclude the pilot
responsibility of the user of this standard to establish appro-
flame.
priate safety and health practices and determine the applica-
1.3 The principal fire-test-response characteristic obtained
bility of regulatory limitations prior to use.
from this test method is the specific optical density of smoke
from the specimens tested, which is obtained as a function of
2. Referenced Documents
time, for a period of 10 min.
2
2.1 ASTM Standards:
1.4 An optional fire-test-response characteristic measurable
D 2843 Test Method for Density of Smoke from the Burn-
with this test method is the mass optical density (see Annex
ing or Decomposition of Plastics
A1), which is the specific optical density of smoke divided by
D 4100 Test Method for Gravimetric Determination of
the mass lost by the specimens during the test.
Smoke Particulates from Combustion of Plastic Materials
1.5 The fire-test-response characteristics obtained from this
D 5424 Test Method for Smoke Obscuration of Insulating
test are specific to the specimen tested, in the form and
Materials Contained in Electrical or Optical Fiber Cables
thickness tested, and are not an inherent property of the
When Burning in a Vertical Cable Tray Configuration
material, product, or assembly.
E84 Test Method for Surface Burning Characteristics of
1.6 This test method does not provide information on the
Building Materials
fire performance of the test specimens under fire conditions
E 176 Terminology of Fire Standards
other than those conditions specified in this test method. For
E 603 Guide for Room Fire Experiments
limitations of this test method, see 5.5.
E 662 Test Method for Specific Optical Density of Smoke
1.7 Use the SI system of units in referee decisions; see
Generated by Solid Materials
IEEE/ASTMSI-10.Theinch-poundunitsgiveninbracketsare
E 906 Test Method for Heat and Visible Smoke Release
for information only.
Rates for Materials and Products
1.8 This test method is used to measure and describe the
E 1354 Test Method for Heat and Visible Smoke Release
response of materials, products, or assemblies to heat and
Rates for Materials and Products Using an Oxygen Con-
flame under controlled conditions, but does not by itself
sumption Calorimeter
incorporate all factors required for fire hazard or fire risk
E 1474 Test Method for Determining the Heat Release Rate
of Upholstered Furniture and Mattress Components or
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire
2
Standards and is the direct responsibility of Subcommittee E05.21 on Smoke and For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Combustion Products. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved April 1, 2004. Published April 2004. Originally Standards volume information, refer to the standard’s Document Summary page on
approved in 1998. Last previous edition approved in 2004 as E 1995 - 04. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
E 1995 – 04a
Composites Using a Bench Scale Oxygen Consumption 3.2.10 sample, n—an amount of the material, product, or
Calorimeter assembly, to be tested, which is representativ
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.