oSIST prEN 54-3:2009
(Main)Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
This European Standard specifies the requirements, test methods and performance criteria for fire alarm sounders in a fixed installation intended to signal an audible warning of fire between a fire detection and fire alarm system and the occupants of a building. It is intended to cover only those devices which derive their operating power by means of a physical electrical connection to an external source such as a fire alarm system.
This standard specifies fire alarm sounders for two types of application environment, type A for indoor use and type B for outdoor use.
This standard is intended to cover voice sounders by the application of additional requirements, tests and performance criteria detailed in Annex C.
This standard is not intended to cover:
a) loudspeaker type devices primarily intended for emitting emergency voice messages;
b) supervisory sounders, for example, within the control and indicating equipment.
Brandmeldeanlagen - Teil 3: Aukausische Alarmlerungseinrichtungen
Systèmes de détection et d'alarme incendie - Partie 3: Dispositifs sonores d'alarme feu
La présente Norme européenne spécifie les exigences, les méthodes d'essai et les critères de performance
pour les dispositifs sonores d'alarme feu d'une installation fixe, destinés à transmettre un avertissement
sonore de feu entre les systèmes de détection et d'alarme incendie et les occupants d'un bâtiment. Elle est
prévue pour ne traiter que les dispositifs fonctionnant au moyen d'un raccordement physique à une source
d'alimentation électrique externe, tel qu'un système d'alarme incendie.
La présente norme est également destinée à couvrir les diffuseurs d'alarme vocale par l'application
d'exigences, d'essais et de critères de performance spécifiques.
La présente norme spécifie les exigences concernant les dispositifs sonores d'alarme feu pour des
environnements d'utilisation de type A, intérieurs et de type B, extérieurs.
La présente norme ne traite pas :
a) des dispositifs de type à haut-parleurs dont la fonction première est de diffuser des messages vocaux
d'urgence générés par une source audio externe ;
b) des dispositifs de signalisation sonores de supervision, par exemple, ceux incorporés dans les
équipements de contrôle et de signalisation.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 3. del: Naprave za alarmiranje - Zvočne naprave
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2009
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO1DSUDYH]D
DODUPLUDQMH=YRþQHQDSUDYH
Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
Brandmeldeanlagen - Teil 3: Aukausische Alarmlerungseinrichtungen
Systèmes de détection et d'alarme incendie - Partie 3: Dispositifs sonores d'alarme feu
Ta slovenski standard je istoveten z: prEN 54-3
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
DRAFT
prEN 54-3
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2009
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 3: Fire alarm
devices - Sounders
Systèmes de détection et d'alarme incendie - Partie 3: Brandmeldeanlagen - Teil 3: Aukausische
Dispositifs sonores d'alarme feu Alarmlerungseinrichtungen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 72.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 54-3:2009: E
worldwide for CEN national Members.
prEN 54-3:2009 (E)
Contents Page
Foreword .4
1 Scope .5
2 Normative references .5
3 Definitions and abbreviations .6
3.1 Definitions .6
3.2 Abbreviations .7
4 Requirements .7
4.1 Compliance .7
4.2 Sound level .7
4.3 Frequency and sound pattern .8
4.4 Requirements for voice sounders.8
4.5 Construction .9
4.6 On-site adjustment of the mode of operation . 10
4.7 Durability . 10
4.8 Marking and data . 10
4.9 Additional requirements for software controlled sounders . 11
5 Tests . 13
5.1 General . 13
5.2 Reproducibility . 14
5.3 Operational performance . 16
5.4 Durability . 16
5.5 Dry heat (operational) . 16
5.6 Dry heat (endurance) . 18
5.7 Cold (operational) . 18
5.8 Damp heat, cyclic (operational) . 20
5.9 Damp heat, steady state (endurance) . 21
5.10 Damp heat, cyclic (endurance) . 21
5.11 Sulfur dioxide (SO ) corrosion (endurance) . 22
5.12 Shock (operational) . 23
5.13 Impact (operational). 24
5.14 Vibration, sinusoidal (operational). 25
5.15 Vibration, sinusoidal (endurance) . 26
5.16 Electromagnetic compatibility (EMC), immunity (operational) . 27
5.17 Enclosure protection . 28
5.18 Operational performance for voice sounders . 30
5.19 Voice sounders sequence timing. 30
5.20 Voice sounders message synchronization . 31
Annex A (normative) Sound level for fire alarm sounders . 33
A.1 General . 33
A.2 Mounting arrangements . 33
A.3 Instrumentation . 33
A.4 Background noise level . 33
A.5 Measurement of sound level . 34
Annex B (normative) Comparative sound level test during environmental conditioning . 38
B.1 General . 38
B.2 Test chamber . 38
B.3 Mounting arrangements . 39
B.4 Instrumentation . 39
prEN 54-3:2009 (E)
B.5 Background noise level . 39
B.6 Test procedure . 39
Annex C (informative) Sound patterns recommended or required in some European countries . 43
C.1 Introduction . 43
C.2 Standards references . 43
C.3 Information on sound patterns . 43
Annex D (informative) Comparison of flammability test requirements in various standards . 46
D.1 Introduction . 46
D.2 Relevant standards . 46
D.3 Vertical burning tests . 47
D.4 Horizontal burning tests . 47
Annex ZA (informative) Clauses addressing the provisions of the EU Construction Products
Directive (89/106/EEC) . 49
ZA.1 Scope and relevant clauses . 49
ZA.2 Procedures for the attestation of conformity of control and indicating equipment covered
by this standard . 50
ZA.3 CE marking and labelling and accompanying documentation . 55
ZA.4 EC certificate and declaration of conformity . 56
prEN 54-3:2009 (E)
Foreword
This document (prEN 54-3:2009) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
This edition of EN 54-3 cancels and replaces EN 54-3:2001, EN 54-3: 2001/A1: 2002 and EN 54-3: 2001/A2:
2006, which have been extensively revised.
Introduction
The purpose of a fire alarm sounder is to warn person(s) within, or in the vicinity of, a building of the
occurrence of a fire emergency situation in order to enable such a person(s) to take appropriate measures.
This standard recognizes that the exact nature of the sound requirements, i.e. its frequency range, temporal
pattern and output level will vary according to the nature of the installation, the type of risk present and
appropriate measures to be taken, the type of signals used by other non-emergency alarms (see, for example,
EN 457) and national differences in custom and practice. The resulting standard specifies, therefore, a
common method for the testing of the operational performance of sounders against the specification declared
by the manufacturer rather than imposing common requirements.
Attention is drawn to ISO 8201:1987, Acoustics – Audible emergency evacuation signal, the international
standard which specifies the temporal pattern and the required sound pressure level of an audible emergency
evacuation signal.
This standard gives common requirements for the construction and robustness of sounders as well as for their
performance under climatic, mechanical and electrical interference conditions which are likely to occur in the
service environment. The sounders have been classified in either an indoor or an outdoor application
environment category.
In fire detection and fire alarm systems, voice sounders are used as alarm devices for warning the occupants
of a building of the occurrence of a fire risk, using a combination of an attention drawing signal and dedicated
voice message(s). The requirements, test methods and performance criteria specified in EN 54-3:2001 for
sounders are also applicable to voice sounders. Additional requirements, test methods and performance
criteria specific to voice sounders are also incorporated.
prEN 54-3:2009 (E)
1 Scope
This European Standard specifies the requirements, test methods and performance criteria for fire alarm
sounders in a fixed installation intended to signal an audible warning of fire detection and fire alarm systems
and the occupants of a building. It is intended to cover only those devices which derive their operating power
by means of a physical electrical connection to external source such as a fire alarm system.
This standard is also intended to cover voice sounders by the application of specific requirements, tests and
performance criteria.
This standard specifies fire alarm sounders for two types of application environment, Type A for indoor use
and Type B for outdoor use.
This standard does not cover:
a) loudspeaker type devices primarily intended for emitting emergency voice messages that are generated
from an external audio source;
b) supervisory sounders, for example, within the control and indicating equipment.
2 Normative references
The following referenced documents are indispensable for the application of this standard. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A1:1998, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A2:2003, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 60068-1:1994, Environmental testing — Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum
1988 + A1:1992)
EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Test A: Cold (IEC 60068-2-1:2007)
EN 60068-2-2:1993, Basic environmental testing procedures — Part 2-2: Tests — Tests B — Dry heat
(IEC 60068-2-2:1974 + IEC 60068-2-2 A:1976)
EN 60068-2-2:1993/A1:1993, Basic environmental testing procedures — Part 2-2: Tests — Tests B — Dry
heat – (IEC 60068-2-2:1974/A1:1993)
EN 60068-2-2:1993/A2:1994, Basic environmental testing procedures — Part 2-2: Tests — Tests B — Dry
heat – (IEC 60068-2-2:1974/A2:1994)
EN 60068-2-6:1995, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal)
(IEC 60068-2-6:1995 + Corrigendum 1995)
EN 60068-2-27:1993, Basic environmental testing procedures — Part 2: Tests — Test Ea and guidance:
Shock (IEC 60068-2-27:1987)
EN 60068-2-30:2005, Environmental testing — Part 2-30: Tests — Test Db: Damp heat, cyclic (12 h + 12 h
cycle) (IEC 60068-2-30:2005)
prEN 54-3:2009 (E)
EN 60068-2-42:2003, Environmental testing — Part 2-42: Tests — Test Kc: Sulphur dioxide test for contacts
and connections (IEC 60068-2-42:2003)
EN 60068-2-75:1997, Environmental testing — Part 2-75: Tests — Test Eh: Hammer (IEC 60068-2-75:1997)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
(IEC 60068-2-78:2001)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989)
EN 60529:1991/A1:2000, Degrees of protection provided by enclosures (IP code) — Amendment A1
(IEC 60529:1989/A1:1999)
EN 60695-11-10:1999, Fire hazard testing — Part 11-10: Test flames — 50 W horizontal and vertical flame
test methods (IEC 60695-11-10:1999)
EN 60695-11-10:1999/A1:2003, Fire hazard testing – Part 11-10: Test flames — 50 W horizontal and vertical
flame test methods – Amendment A1 (IEC 60695- 11-10:1999/A1:2003
EN 60695-11-20:1999, Fire hazard testing — Part 11-20: Test flames — 500 W flame test methods
(IEC 60695-11-20:1999)
EN 60695-11-20:1999/A1:2003, Fire hazard testing — Part 11-20: Test flames — 500 W flame test methods)
— Amendment A1 (IEC 60695-11- 20:1999/A1:2003)
EN 61672-1:2003, Electroacoustics. Sound level meters. Specifications (IEC 61672-1:2002)
EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000)
3 Definitions and abbreviations
For the purposes of this European Standard, the following terms and definitions and those given in EN 54-1
apply.
3.1 Definitions
3.1.1
A-weighted sound level
sound pressure, expressed in dB(A), which is 20 times the logarithm to base ten of the ratio of the A-weighted
sound pressure to the reference pressure of 20 µPa at 1 kHz
NOTE The A-weighting characteristics are given in IEN 61672-1:2003
3.1.2
fire alarm sounder
sounder generating device intended to signal an audible warning of fire between a fire detection and fire alarm
system and the occupants of a building
3.1.3
mode (of operation)
one of a possible number of pre-defined sound of the audible alarm device which can be selected by means
specified by the manufacturer
EXAMPLE Sound patterns, sound levels.
3.1.4
reference point
point representing the origin of the sound within or on the surface of the sounder as specified by the
manufacturer
prEN 54-3:2009 (E)
NOTE The reference point is used in Annex A.
3.1.5
sound pattern
pre-defined acoustic alarm signal
NOTE Sound pattern is also often referred to as tone.
3.1.6
supervisory sounder
audible device on a piece of equipment used for drawing attention to a change of status
NOTE Supervisory sounders are often mounted within the fire detection and fire alarm control and indicating
equipment.
3.1.7
type A sounder
device primarily intended for indoor applications
NOTE Type A sounders may be suitable for some protected outdoor situations.
3.1.8
type B sounder
device primarily intended for outdoor applications
NOTE Type B sounders may be more suitable than type A sounders for some indoor situations where high
temperature and/or humidity are present.
3.1.9
volume control
means for adjusting sound level
3.2 Abbreviations
AC Alternating current
DC Direct current
RMS Root mean square
VAD Visual alarm device
4 Requirements
4.1 Compliance
In order to comply with this standard, sounders shall meet the requirements of this clause, which shall be verified
by visual inspection or engineering assessment and shall be tested as described in clause 5 and shall meet the
requirements of the tests.
4.2 Sound level
The standard requires that the manufacturer declare sound levels in the data required under 4.6.2. The
manufacturer may declare different sound levels for operation under different conditions, for example, when
operating on different voltage ranges or with different sound patterns. If this is the case the sound level of
each specimen shall be measured under each mode of operation (see 5.3).
prEN 54-3:2009 (E)
When tested in accordance with 5.3 the fire alarm sounder shall produce A-weighted sound levels of at least
65 dB in one direction.
NOTE A maximum sound level received by occupants may be specified by National regulations.
4.3 Frequency and sound pattern
This standard covers sounders which produce different frequencies and sound patterns and, therefore, does
not specify a minimum and maximum frequency or specific sound pattern. However, the main sound
frequency(ies), frequency range(s) and sound pattern(s) shall be declared in the data required under 4.8.2.
NOTE 1 The sound patterns and frequencies required may vary in different countries. Reference needs to be made to
local regulations.
NOTE 2 Annex C gives information on some of the national standards that applies in Europe and on ISO 8201.
ISO 8201 specifies a standard international evacuate signal.
4.4 Requirements for voice sounders
4.4.1 General
Voice sounders shall be capable of producing an audible warning signal and a voice message or messages.
All messages related to fire safety shall be declared by the manufacturer and shall be considered by the
testing authority. The message determined to be worst case shall be subject to the conformance assessment.
NOTE 1 When selecting the worst case message, message length, loudness and repetition timing should be
considered.
For messages that require immediate action, the warning signal and message sequence broadcast by the
device shall be within the following limits:
warning signal, lasting for 2 s to 10 s; followed by
silence, lasting for 0,25 s to 2 s; followed by
voice message; followed by
silence, lasting for 0,25 s to 5 s.
The time for each cycle shall not exceed 30 s.
The periods of silence may need to be longer than indicated in certain circumstances, for example in spaces
with long reverberation times, but shall not be such that the time between the start of each cycle exceeds
30 s.
NOTE 2 For other messages, it is permitted to extend either or both the silence period after the voice message and the
period within which the message is repeated.
Access to the message recording function shall be restricted as specified in 4.7.4.
NOTE 3 Persons trained in the proper use of microphones should be used to record the messages. The recordings
should be made in a room with a controlled acoustic environment having an ambient noise level not greater than 30 dBA
and a reverberation time not greater than 0,5 s from 150 Hz to 10 kHz.
prEN 54-3:2009 (E)
4.4.2 Synchronization – Optional function
Voice alarm indicators may interact acoustically when they are installed in close proximity. To prevent this,
voice sounders may have provision for synchronising warning signals and messages with that of other
devices. Message synchronization shall meet the requirements of 5.20.3.
When power interruption is used for synchronisation purposes, this shall not adversely affect the warning
signal or the voice message.
NOTE Synchronisation can be achieved by internal circuitry, the addition of a trigger wire connected between devices
or by other means as defined by the manufacturer.
4.5 Construction
4.5.1 Provision for external conductors
4.5.1.1 The sounder shall provide space within its enclosure for external conductors to be brought in and
terminated. Entry holes for conductors or cables shall be provided or the location where such holes are to be
made shall be indicated, by providing a template or some other suitable means.
4.5.1.2 Terminals for connecting external conductors shall be designed so that the conductors are
clamped between metal surfaces without being damaged.
4.5.2 Materials
The sounder shall be constructed of material(s) capable of withstanding the tests described in 5.2 to 5.17. In
addition, the material(s) of plastic enclosures shall meet the following flammability requirements:
EN 60695-11-10:1999 as amended by EN 60695-11-10:1999/A1:2003 Class V-2 or HB75 for devices
operating from a voltage source less than or equal to 30 V RMS. or 42,4 V DC and consuming less than
15 W of power;
EN 60695-11-20:1999 as amended by EN 60695-11-20:1999/A1:2003 Class 5VB for devices operating from a
voltage source greater than 30 V RMS. or 42,4 V DC and consuming more than 15 W of power.
NOTE Verification of conformance to 4.5.2 a) and 4.5.2 b) can be carried out by examination of a Certificate of
Conformity for the material used in the construction of the enclosure (see Annex D).
4.5.3 IP ratings
The degree of protection provided by the enclosure of the sounders shall meet the following requirements:
for Type A audible alarm devices – Sounder: Code IP21C of EN 60529:1991 as amended by
EN 60529:1991/A1:2000;
for Type B audible alarm devices – Sounder: Code IP33C of EN 60529:1991 as amended by
EN 60529:1991/2000.
4.5.4 Access
Means shall be provided to limit access for removal of parts or the whole device and to make adjustment to
the mode of operation, e.g. special tool, codes, hidden screws, seals, etc.
NOTE The use of a special tool is intended to discourage unauthorized persons from easily accessing the
equipment.
prEN 54-3:2009 (E)
4.6 On-site adjustment of the mode of operation
If there is provision for on-site adjustment of the mode of operation of the sounder:
for each setting, at which the manufacturer claims compliance with this standard, the sounder shall comply
with 4.5.4.
any setting(s), at which the manufacturer does not claim compliance with this standard, shall comply with
4.5.4 and:
for volume controls, the limits of the compliant range of sound levels shall be clearly marked on the
sounder and shown in the associated data,
for sound pattern, the compliant setting(s) shall be clearly marked in the associated data.
NOTE These adjustments may be carried out at the sounder or at the control and indicating equipment.
4.7 Durability
The sounder shall be rated for at least 100 hours operation. No limitation by the manufacturer on duty factor
or maximum on-time shall prevent the device from operating the 1 h 'on' 1 h 'off' cycle required by the test
procedure described in 5.4.
NOTE This requirement does not apply to the capacity of batteries which may be used within sounders as a means
of local storage of operating power. The capacity and charging requirements of such batteries need to meet the
requirement of the system.
4.8 Marking and data
4.8.1 Marking
Each fire alarm sounder shall be clearly marked with the following information:
number of this standard (i.e. EN 54-3);
environmental type, [i.e. Type A or Type B (see clause 3)];
name or trademark of the manufacturer or supplier;
manufacturer or supplier model designation (type or number);
terminal designations;
rated supply voltages or voltage ranges (AC. or DC.);
a mark(s) or code(s) (for example, serial number or batch code), by which the manufacturer can identify, at
least, the date or batch and place of manufacture, and the version number(s) of any software contained
within the device.
Where any marking on the device uses symbols or abbreviations not in common use then these shall be
explained in the data supplied with the device.
The marking need not be discernible when the device is installed and ready for use but shall be visible during
installation and shall be accessible during maintenance.
The markings shall not be placed on screws or other easily removable parts.
prEN 54-3:2009 (E)
4.8.2 Data
The information required in 4.7.1 together with the following shall be supplied with the device, or shall be given
in a data sheet or technical manual identified on, or with each device:
operating voltage range(s);
maximum and/or average current consumption, where applicable;
NOTE For sounders used in an addressable system, it may not be relevant to declare the current consumption as
system configuration and the loading of addressable circuit(s) is configured at the control and indicating equipment.
for all modes of operation,
for all specified modes of operation for which compliance with this standard is claimed, the minimum A-
weighted sound level in dB(A) at a distance of 1 m from the reference point of the device for the following
directions of radiation:
surface mounted device: at 30º intervals from 15º to 165º through a semi-circular arc in font of the device
and centred at the intersection of its normal mounting surface and its principal axis, for two
perpendicular planes corresponding to the horizontal and vertical planes of the device in its designed
position (see Annex A, Figure A3),
pole mounted device: at 30º intervals through a 360º circle centred at the intersection of the horizontal
plane containing its principal axis and the vertical line through the geometric centre of the sound
diffusing assembly, for two perpendicular planes corresponding to the horizontal and vertical planes
of the device in its designed position (see Annex A, Figure A3);
sound pattern(s) that comply with this standard and, where applicable, sound pattern(s) that comply with
national standards;
IP code to EN 60529:1991 as amended by EN 60529:1991/A1:2000 ;
any other information necessary to allow correct installation, operation and maintenance of the device.
4.9 Additional requirements for software controlled sounders
4.9.1 General
For sounders which rely on software control in order to fulfil the requirements of this standard, the
requirements of 4.9.2, 4.9.3 and 4.9.4 shall be met.
4.9.2 Software documentation
4.8.2.1 The manufacturer shall submit documentation which gives an overview of the software design.
This documentation shall be in sufficient detail for the design to be inspected for compliance with this standard
and shall include at least the following:
a functional description of the main program flow (e.g. as a flow diagram or structogram) including:
1) a brief description of the modules and the functions that they perform;
2) the way in which the modules interact,
3) the overall hierarchy of the program,
4) the way in which the software interacts with the hardware of the sounder,
prEN 54-3:2009 (E)
5) the way in which the modules are called, including any interrupt processing.
a description of which areas of memory are used for the various purposes (e.g. the program, site specific data
and running data);
a designation, by which the software and its version can be uniquely identified.
4.8.2.2 The manufacturer shall have available detailed design documentation, which only needs to be
provided if required by the testing authority. It shall comprise at least the following:
an overview of the whole system configuration, including all software and hardware components;
c) a description of each module of the program, containing at least:
the name of the module,
a description of the tasks performed,
a description of the interfaces, including the type of data transfer, the valid data range and the checking
for valid data.
d) full source code listings, as hard copy or in machine-readable form (e.g. ASCII-code), including all global
and local variables, constants and labels used, and sufficient comment for the program flow to be
recognized;
e) details of any software tools used in the design and implementation phase (e.g. CASE-tools, compilers).
4.9.3 Software design
In order to ensure the reliability of the sounder, the following requirements for the software design shall apply:
the software shall have a modular structure;
the design of the interfaces for manually and automatically generated data shall not permit invalid data to
cause error in the program operation;
the software shall be designed to avoid the occurrence of deadlock of the program flow.
4.9.4 The storage of programme and data
The programme necessary to comply with this standard and any preset data, such as manufacturer's settings,
shall be held in non-volatile memory. Writing to areas of memory containing this program and data shall only
be possible by the use of some special tool or code and shall not be possible during normal operation of the
sounder.
Site-specific data shall be held in memory which will retain data for at least two weeks without external power
to the sounder, unless provision is made for the automatic renewal of such data, following loss of power,
within 1 h of power being restored.
prEN 54-3:2009 (E)
5 Tests
5.1 General
5.1.1 Atmospheric conditions for tests
Unless otherwise stated in a test procedure, the testing shall be carried out after the test specimen has been
allowed to stabilize in the standard atmospheric conditions for testing described in EN 60068-1:1994, as
follows:
temperature: 15 ºC to 35 ºC;
relative humidity: 25 % to 75 %;
air pressure: 86 kPa to 106 kPa.
The temperature and humidity shall be substantially constant for each test where these standard atmospheric
conditions are applied.
5.1.2 Operating conditions for tests
If a test method requires a specimen to be sounding, then the specimen shall be connected to suitable power
suitable power supply equipment as specified in the data provided by the manufacturer. Where, in order to be
sounding, a specimen also requires the application of a control signal or signals, this shall be provided in
accordance with the data provided by the manufacturer and the control signals shall be arranged so that the
specimen is in a non-sounding state.
Unless otherwise specified in the test procedure, the supply parameters applied to the specimen shall be set
within the manufacturer's specified range(s) and shall remain constant throughout the tests. The value chosen
for each parameter shall be the nominal value, or the mean of the specified range.
If the manufacturer has declared different sound levels for operation under different conditions (see 4.8.2), then,
unless otherwise specified in the test procedure, the tests shall be conducted under one selected mode of
operation only. Selection of the mode of operation shall be made with the aim to use that which consumes the
most power. This will normally be the most continuous or the loudest mode.
NOTE All modes of operation and all voltages are tested in 5.3.
5.1.3 Mounting arrangements
Unless otherwise specified, the specimen shall be mounted by its normal means of attachment in accordance
with the manufacturer's instructions on a flat rigid backing board. If these instructions describe more than one
method of mounting then the method considered to be most unfavourable shall be chosen for each test.
The detailed mounting arrangements are given in Annex A or Annex B for the different sound level tests used.
5.1.4 Tolerances
The tolerances for the environmental test parameters shall be given in the basic reference standards for the
test (e.g. the relevant part of EN 60068).
If a specific tolerance or deviation limit is not specified in a requirement or test procedure, then a deviation
limit of ± 5% shall be applied.
5.1.5 Provision for tests
The following shall be provided for testing compliance with this European Standard:
prEN 54-3:2009 (E)
eight specimens of type A or ten specimens of type B sounder with any mounting, bases, boxes or
accessories etc.;
any equipment, such as control and indicating equipment, as may be necessary for the correct operation of
the device in accordance with the manufacturer's specification;
the data required in 4.8.2.
The specimens submitted shall be deemed representative of the manufacturer's normal production with
regard to their construction and settings.
NOTE The details of the power supply equipment used and/or the equipment used for generating the control
signal(s) should be given I the test report.
5.1.6 Test schedule
The specimens shall be tested and inspected according to the schedule given in Table 1.
All the specimens shall be first submitted to the reproducibility test described in 5.2. On completion of the
reproducibility test, the specimen with the least loud sound level shall be numbered 1 and the rest arbitrarily
numbered from 2 to 8 for type A or 2 to 10 for type B.
Unless otherwise required by the test procedure, the mode of operation selected for conducting the
reproducibility test shall be used for the other tests.
Where, after one of the test specified in 5.5 to 5.16 the sound level of the specimen differs from that measured
during the reproducibility test by more than 6 dB, a new specimen shall be used for the next test on the
schedule for that specimen. The sound level shall be first measured as specified in 5.2.
The tests on an individual specimen may be carried out in any order except that the reproducibility test (5.2)
shall be performed first on all specimens and the tests on specimens 1 and 2 shall be carried out in the order
listed (i.e. 5.20 last).
5.2 Reproducibility
5.2.1 Object of the test
To show that the sound output of the sounder does not vary unduly from specimen to specimen and to
establish sound output data for comparison with the sound output measured during and/or after the
environmental tests specified in this standard.
5.2.2 Test procedure
The A-weighted sound levels of all the specimens shall be measured as described in Annex B.
The measurement shall be recorded in dB for each specimen and the sound level of the loudest and the least
L L
max min
loud specimen shall be represented by and respectively.
5.2.3 Test requirements
The audible alarm device shall be deemed to comply with the requirement of this clause if the difference
L L
max min
between and is less than 6 dB.
prEN 54-3:2009 (E)
Table 1 — Schedule of tests
Specimen No(s)
Test Subclause
Type A Type B
Reproducibility (frequency response / sensitivity) 5.2 all all
a
Operational performance 5.3 1 1
Durability 5.4 2 2
Dry heat (operational) 5.5 3 3
Dry heat (endurance) 5.6 - 9
Cold (operational) 5.7 3 3
Damp heat, cyclic (operational) 5.8 3 3
Damp heat, steady state (endurance) 5.9 3 3
Damp heat, cyclic (endurance) 5.10 - 10
SO corrosion (endurance) 5.11 4 4
Shock (operational) 5.12 5 5
Impact (operational) 5.13 6 6
Vibration (operational) 5.14 7 7
Vibration (endurance) 5.15 7 7
b
Electromagnetic compatibility (EMC) tests (operational) 5.16
Electrostatic discharge (operational) 8 8
Radiated electromagnetic fields (operational) 8 8
Conducted disturbances induced by electromagnetic fields (operational) 8 8
Voltage transients, fast transient bursts (operational) 8 8
Voltage transients, slow high energy voltage surge (operational) 8 8
Enclosure protection 5.17 1,2 1,2
Operational performance, additional test for voice sounders 5.18 1 1
Voice sounders sequence timing 5.19 2 2
Voice sounders message synchronization 5.20 1, 2 1, 2
a
For voice sounders, only the warning signal shall be measured
b
The tests specified in 5.16 are not required for sounders which do not rely on active electronic components for their operation.
prEN 54-3:2009 (E)
5.3 Operational performance
5.3.1 Object of the test
To check that the sound levels declared by the manufacturer can be achieved within the specified range(s) of
supply parameters (e.g. voltage).and is not unduly dependent on these parameters.
5.3.2 Test procedure
The sound level of the specimen shall be measured in free field conditions using the test method described in
Annex A with the supply parameters at the maximum and minimum of the specified range(s) [see 4.8.2 a) and
b)].
If the manufacturer has declared different sound levels and different operating frequencies for different modes
of operation [see 4.8.2], then the sound level of the specimen shall be measured under each mode.
5.3.3 Test requirements
The sounder shall be deemed to comply with the requirements of this clause if, for each mode of operation:
the A-weighted sound level is greater than 65 dB in at least one direction;
f) the sound level measured at each of the specified angles is not less than that declared by the
manufacturer [see 4.8.2 c)].
5.4 Durability
5.4.1 Object of the test
To show that the sound level does not change significantly after prolonged operation of the audible alarm device.
5.4.2 Test procedure
The specimen shall be subjected to the following durability cycle 100 times: the specimen shall be operated for
1 h at the maximum of the supply parameters declared by the manufacturer (see 4.8.2) and then shall be left in
the non-operating condition for 1 h. The sound level shall be measured as described in Annex B within 1 h of the
final period of operation.
5.4.3 Test requirement
The sounder shall be deemed to comply with the requirements of this clause if the A-weighted sound level
measured after 100 durability cycles does not decrease by more than 6 dB from that measured, for the same
specimen, under the same operating condition, in the reproducibility test (see 5.2).
5.5 Dry heat (operational)
5.5.1 Object of the test
To demonstrate the ability of the sounder to function correctly at high ambient temperatures, which may occur
for short periods in the service environment.
prEN 54-3:2009 (E)
5.5.2 Test procedure
5.5.2.1 Reference
The test apparatus and procedure shall be as described in EN 60068-2-2:1993 as amended by EN 60068-2-
2:1993/A1:1993 and EN 60068-2-2:1993/A2:1994, Test Bb for non-heat dissipating specimens or Test Bd for
heat dissipating specimens, except that the test shall be conducted in a reverberation chamber as described
in annex B.
5.5
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.