ISO 7240-33:2026
(Main)Fire detection and alarm systems — Part 33: Thermal image fire detectors
- Abstract
This document specifies requirements, test methods and performance criteria for thermal image fire detectors (TIFD), which operate in the infrared spectrum, for use in fire detection and alarm systems installed in and around buildings. Detectors developed for the protection of specific risks that incorporate special characteristics (including additional features or enhanced functionality for which this document does not define a test or assessment method) are beyond the scope of this document.
- Status
- Published
- Publication Date
- 16-Nov-2026
- Technical Committee
- ISO/TC 21/SC 3 - Fire detection and alarm systems
- Drafting Committee
- ISO/TC 21/SC 3 - Fire detection and alarm systems
- Current Stage
- 6060 - International Standard published
- Start Date
- 17-Nov-2026
- Completion Date
- 17-Nov-2026
ISO 7240-33:2026 is an ISO standard for thermal image fire detectors (TIFD) used in fire detection and alarm systems installed in and around buildings. It specifies the requirements, test methods and performance criteria for detectors that work in the infrared spectrum, so manufacturers, test laboratories, installers and buyers can judge whether a TIFD is suitable for a project.
What does ISO 7240-33:2026 specify?
ISO 7240-33:2026 covers thermal image fire detectors that detect fire by analysing thermal images rather than by sensing combustion products directly. It applies to detectors used in and around buildings, and it excludes detectors for specific risks when they include special characteristics or extra functions for which the document does not define a test or assessment method.
The document is organized into eight clauses and three normative annexes:
| Part | What it covers |
|---|---|
| Annex A | Fire test room |
| Annex B | Flaming liquid (n-heptane) fire (TF5) |
| Annex C | Smoke-measuring instruments |
Clause 1 gives the scope, Clause 2 lists normative references, Clause 3 defines terms, Clause 4 states requirements, Clause 5 gives the test programme, Clause 6 covers the test report, Clause 7 covers marking, and Clause 8 covers the data the manufacturer has to provide.
What are the key requirements of ISO 7240-33:2026?
ISO 7240-33:2026 requires a TIFD to meet the Clause 4 requirements, pass the Clause 5 tests, and be marked and documented according to Clauses 7 and 8. In practice, this means the detector is not assessed only by design claims - it must also prove its behaviour under test and in the supplied technical information.
Fire detection behaviour and alarm functions
The manufacturer has to declare what stimulus the TIFD is designed to respond to. Clause 4.2 states that the response stimulus shall consist of objects radiating in the infrared wavelength and may also include flames. That matters because the declared sensing principle has to match how the detector is intended to be used and tested.
Clause 4.4 requires the manufacturer to declare the fire detection range and the size of the hot object detectable at that distance. Clause 5.8 then checks response at the declared minimum and maximum distance using a calibrated black body source. For users, this means the installed detector must match the distance and target size used in the design of the system.
Clause 4.5 requires a fault signal if complete obscuration of the camera lens prevents fire detection in the operating field of view. Clause 4.8 adds that detachable cameras need a means to detect disconnection and give a fault signal. These requirements matter because a blocked or disconnected imaging path must not fail silently.
Alarm indication, sharing of transmission paths and settings
Clause 4.6 requires an integral red visual indicator when the detector does not display the field of view to the user. The indicator has to identify which detector is alarming, and other visual conditions have to remain clearly distinguishable. This helps installers and operators locate the source of an alarm quickly.
Clause 4.9 covers systems where more than one TIFD shares the transmission path to the fire detection control and indicating equipment (FDCIE). A single transmission fault must not stop alarm signalling from more than one TIFD, and one TIFD fault must not block alarms from another. This is important in distributed systems where one failure should not take down the whole loop.
Clause 4.10 and 4.11 control manufacturer settings and on-site adjustment of response behaviour. Conformance settings must be protected by a special means, and any non-conforming setting has to be clearly identified as non-conforming. This limits accidental changes during installation or maintenance.
Environmental and enclosure performance
Clause 4.12 requires the manufacturer to declare an enclosure protection rating in accordance with IEC 60529. The document associates indoor use with IP30 and outdoor use with IP54 or higher, and it allows higher ratings if the manufacturer declares them. Clause 4.13 requires declaration of the operating temperature class, with separate classes for indoor controlled, indoor, Outdoor 1 and Outdoor 2 use.
These declarations matter because the test programme in Clause 5 checks the detector at the declared environmental limits, including dry heat, cold, damp heat, ingress protection, shock, vibration, sulfur dioxide corrosion and EMC immunity.
Software and stored data
Clause 4.14 applies when software is used to fulfil the document requirements. The software design has to be modular, the interfaces have to reject invalid data, and the program flow has to avoid deadlock. The required program and preset data must be held in non-volatile memory, and site-specific data must survive power loss for at least two weeks unless it is automatically restored within 1 h after power returns.
For a buyer or integrator, this means the detector’s software behaviour and stored settings are part of conformance, not just internal implementation details.
Testing and optional claims
Clause 5 includes the key performance tests. Repeatability checks stability on repeated alarms, reproducibility checks variation between specimens, and pixel array uniformity checks that sensitivity does not vary too much across the image. Optional tests cover fire sensitivity to TF5 and moving object immunity, so these claims must be supported only when the manufacturer declares them.
Clause 5.6 uses a TF5 flaming liquid fire in the fire test room from Annex A and Annex B, with smoke measurement supported by Annex C. That gives the standard its core fire-response validation method.
What terms does ISO 7240-33:2026 define?
- thermal image fire detector (TIFD) - A self-contained device or distributed system that analyses thermal images to measure temperature and detect the likely presence of fire.
- controller - Information technology equipment that records and/or performs analytics on images; it may be remote from the sensor.
- response threshold value (RTV) - The temperature at which the detector signals an alarm in the specified response test.
- field of view (FOV) - The image captured by the thermal image fire detector, expressed as an angle or as width and height at a stated distance.
- fire detection control and indicating equipment (FDCIE) - The equipment to which the TIFD transmission path connects for alarm and fault signalling.
- electromagnetic compatibility (EM) - The document’s abbreviation for electromagnetic compatibility, used in the EMC immunity test.
- IP - The enclosure protection rating framework used for dust and water ingress protection in accordance with IEC 60529.
Who uses ISO 7240-33:2026?
ISO 7240-33:2026 is used by manufacturers of thermal imaging fire detectors, especially those building self-contained or distributed sensor-controller systems. It is also used by test laboratories and certification bodies that need to run the fire, environmental, ingress and EMC tests, and by system designers, installers and commissioning engineers who need the detector to interface correctly with the rest of the fire alarm system.
Quality managers and buyers use it to compare products on declared range, operating temperature, enclosure protection, software control, marking and documentation. Maintenance teams also use the marking and documentation clauses when checking compatibility, installation constraints and service procedures.
Which standards are used with ISO 7240-33:2026?
ISO 7240-33:2026 refers to these standards in Clause 2 and uses them directly in its test methods:
- IEC 60068-2-1 - cold testing for low-temperature conditioning.
- IEC 60068-2-2 - dry heat testing for high-temperature conditioning.
- IEC 60068-2-6 - sinusoidal vibration testing.
- IEC 60068-2-27 - shock testing.
- IEC 60068-2-42 - sulfur dioxide corrosion testing.
- IEC 60068-2-75 - hammer impact testing.
- IEC 60068-2-78 - damp heat, steady-state testing.
- IEC 60529 - IP enclosure protection ratings.
- IEC 62262 - IK mechanical impact ratings and the spring hammer method used for camera impact tests.
- IEC 62599-2 - EMC immunity requirements for fire and security alarm system components.
What does the ISO 7240-33:2026 document contain?
ISO 7240-33:2026 contains detailed test procedures for repeatability, reproducibility, pixel array uniformity, lens blocking, distance response, supply variation, environmental endurance and EMC immunity. It also includes optional fire sensitivity testing with TF5 and optional moving object immunity testing, so a manufacturer can claim these behaviours only when they are tested.
Annex A defines the fire test room and instrument placement. Annex B defines the TF5 flaming liquid fire, including the fuel, tray arrangement, ignition and validity criteria. Annex C defines the smoke-measuring instruments and gives the measurement principles and technical data for the obscuration meter and measuring ionization chamber.
Clause 6 specifies what the test report has to record, including response threshold values, conditioning atmosphere, room conditions and any deviations or optional operations. Clause 7 sets the marking information, and Clause 8 sets the technical data package, including software, hardware, installation and user documentation.
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
ISO 7240-33:2026 is a standard published by the International Organization for Standardization (ISO). Its full title is "Fire detection and alarm systems — Part 33: Thermal image fire detectors". This standard covers: This document specifies requirements, test methods and performance criteria for thermal image fire detectors (TIFD), which operate in the infrared spectrum, for use in fire detection and alarm systems installed in and around buildings. Detectors developed for the protection of specific risks that incorporate special characteristics (including additional features or enhanced functionality for which this document does not define a test or assessment method) are beyond the scope of this document.
This document specifies requirements, test methods and performance criteria for thermal image fire detectors (TIFD), which operate in the infrared spectrum, for use in fire detection and alarm systems installed in and around buildings. Detectors developed for the protection of specific risks that incorporate special characteristics (including additional features or enhanced functionality for which this document does not define a test or assessment method) are beyond the scope of this document.
ISO 7240-33:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 7240-33:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
International
Standard
ISO 7240-33
First edition
Fire detection and alarm systems —
2026-11
Part 33:
Thermal image fire detectors
Systèmes de détection d'incendie et d'alarme —
Partie 33: Détecteurs d'incendie utilisant l'imagerie thermique
Reference number
© ISO 2026
All rights reserved.
This ISO publication is protected by copyright and is owned by ISO and/or its licensors.
The content of this ISO publication is provided under licence, not sold. Use is subject to the applicable licence terms issued by ISO,
an ISO member body, or an authorized third-party distributor.
Except as required for implementation or expressly permitted by a separate licence, no part of this ISO publication may be
reproduced, distributed, modified, used, or made available in any form or by any means – electronic or mechanical, including
photocopying, scanning, recording, or posting on internal or external digital platforms.
Any use beyond the scope of the granted rights is prohibited and may result in legal action.
ISO copyright office
CP 401 • CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
Contents Page
Foreword .vi
Introduction .vii
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
3.1 Definitions .1
3.2 Abbreviated terms .2
4 Requirements . 2
4.1 Conformity .2
4.2 Fire phenomena .3
4.3 Immunity to unwanted alarms .3
4.4 Detection range.3
4.5 Camera lens monitoring .3
4.6 Individual alarm indication .3
4.7 Connection of ancillary devices.3
4.8 Monitoring of detachable cameras .3
4.9 Connection of more than one TIFD to the FDCIE transmission path .3
4.10 Manufacturer's adjustments .4
4.11 On-site adjustment of response behaviour .4
4.12 Protection against the ingress of foreign bodies .4
4.13 Operating temperature .4
4.14 Software .5
4.14.1 General .5
4.14.2 Software design .5
4.14.3 Storage of programs and data .5
5 Tests . 5
5.1 General .5
5.1.1 Atmospheric conditions for tests.5
5.1.2 Mounting arrangements .6
5.1.3 Operating conditions for tests.6
5.1.4 Tolerances .6
5.1.5 Provision for tests .6
5.1.6 Measurement of response threshold value .6
5.1.7 Test schedule .7
5.1.8 Test report .8
5.2 Repeatability .8
5.2.1 Object of test.8
5.2.2 Test procedure.8
5.2.3 Requirements .8
5.3 Reproducibility .8
5.3.1 Object of test.8
5.3.2 Test procedure.9
5.3.3 Requirements .9
5.4 Pixel array uniformity .9
5.4.1 Object of test.9
5.4.2 Test procedure.9
5.4.3 Requirements .9
5.5 Detector lens blocking .9
5.5.1 Object of test.9
5.5.2 Test procedure.9
5.5.3 Requirements .9
5.6 Fire sensitivity (optional) .10
5.6.1 Object of test.10
iii
5.6.2 Test procedure.10
5.6.3 Requirements .11
5.7 Moving object immunity (optional) .11
5.7.1 Object of test.11
5.7.2 Test procedure.11
5.7.3 Requirements . 12
5.8 Response at maximum and minimum distance . 12
5.8.1 Object of test. 12
5.8.2 Test procedure. 12
5.8.3 Requirements . 12
5.9 Variation in supply parameters . 12
5.9.1 Object of test. 12
5.9.2 Test procedure. 12
5.9.3 Final measurements . 13
5.9.4 Requirements . 13
5.10 Dry heat (operational) — Indoor and Outdoor 2 . 13
5.10.1 Object of test. 13
5.10.2 Test procedure. 13
5.10.3 Requirements .14
5.11 Dry heat (operational) — Outdoor 1 .14
5.11.1 Object of test.14
5.11.2 Test procedure.14
5.11.3 Requirements . 15
5.12 Cold (operational) — Indoor . 15
5.12.1 Object of test. 15
5.12.2 Test procedure. 15
5.12.3 Requirements .16
5.13 Cold (operational) — Outdoor 1 and Outdoor 2 .16
5.13.1 Object of test.16
5.13.2 Test procedure.16
5.13.3 Requirements .17
5.14 Cold controllers (operational) .17
5.14.1 Object of test.17
5.14.2 Test procedure.17
5.14.3 Requirements .18
5.15 Damp heat, steady-state (operational) .18
5.15.1 Object of test.18
5.15.2 Test procedure.18
5.15.3 Requirements .18
5.16 Damp heat, steady-state (endurance) .19
5.16.1 Object of test.19
5.16.2 Test procedure.19
5.16.3 Requirements .19
5.17 Protection against ingress of foreign bodies (endurance) .19
5.17.1 Object of test.19
5.17.2 Enclosure of the TIFD . 20
5.17.3 Test procedure. 20
5.17.4 Requirements . 20
5.18 Sulfur dioxide (SO ) corrosion (endurance) . 20
5.18.1 Object of test. 20
5.18.2 Test procedure.21
5.18.3 Requirements .21
5.19 Shock (operational) .21
5.19.1 Object of test.21
5.19.2 Test procedure.21
5.19.3 Requirements . 22
5.20 Impact (operational) for cameras . 22
5.20.1 Object of test. 22
5.20.2 Test procedure. 22
iv
5.20.3 Requirements . 23
5.21 Impact (operational) for controllers . 23
5.21.1 Object of test. 23
5.21.2 Test procedure. 23
5.21.3 Requirements .24
5.22 Vibration, sinusoidal (endurance) .24
5.22.1 Object of test.24
5.22.2 Test procedure.24
5.22.3 Requirements . 25
5.23 Vibration, sinusoidal controller (endurance) . 25
5.23.1 Object of test. 25
5.23.2 Test procedure. 25
5.23.3 Requirements . 26
5.24 Electromagnetic compatibility (EMC) immunity (operational) . 26
5.24.1 Object of test. 26
5.24.2 Test procedure. 26
5.24.3 Requirements .27
6 Test report .27
7 Marking . .27
8 Data .28
8.1 Software documentation . 28
8.2 Hardware documentation . 29
8.3 Installation and user documentation . 29
Annex A (normative) Fire test room .31
Annex B (normative) Flaming liquid (n-heptane) fire (TF5) .33
Annex C (normative) Smoke-measuring instruments .35
Bibliography . 41
v
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire
fighting, Subcommittee SC 3, Fire detection and alarm systems.
A list of all parts in the ISO 7240 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
vi
Introduction
A thermal image fire detection system differs from some point-type detectors (e.g. those specified in
ISO 7240-6 or ISO 7240-7) in that the detection is performed remotely from the actual fire and therefore
does not involve sensor contact with the products of combustion. The fire detection is based on mathematical
algorithm analysis of a thermal image. The thermal image from a thermal camera can be processed by
software to determine the presence of heat or flame, or both (depending on the capability of the system),
which is visible in the image.
Thermal image fire detectors consist of three elements: a sensor, a controller, and a transmission path
between the sensor and image processor. The elements can be in a single cabinet, or the sensor and processor
can be in separate cabinets, interconnected by a transmission path.
The processor incorporates an alarm and fault signalling interface to connect to a compatible fire detection
control and indicating equipment transmission path.
In this document, two enclosure protection ratings are specified for dust and water ingress protection.
Three environmental temperature ranges are specified in this document, for detectors suitable for
installation indoors or outdoors.
A fire detection and alarm system is required to function satisfactorily not only in the event of fire, but also
during and after exposure to conditions likely to be met in practice, including corrosion, vibration, direct
impact, indirect shock and electromagnetic interference. Tests in this document are intended to assess the
performance of the thermal image fire detectors under such conditions.
This document is not intended to place any other restrictions on the design and construction of thermal
image fire detectors.
vii
International Standard ISO 7240-33:2026(en)
Fire detection and alarm systems —
Part 33:
Thermal image fire detectors
1 Scope
This document specifies requirements, test methods and performance criteria for thermal image fire
detectors (TIFD), which operate in the infrared spectrum, for use in fire detection and alarm systems
installed in and around buildings.
Detectors developed for the protection of specific risks that incorporate special characteristics (including
additional features or enhanced functionality for which this document does not define a test or assessment
method) are beyond the scope of this document.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
IEC 60068-2-1, Environmental testing — Part 2-1: Tests — Tests A: Cold
IEC 60068-2-2, Environmental testing — Part 2-2: Tests — Tests B: Dry heat
IEC 60068-2-6, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal)
IEC 60068-2-27, Environmental testing — Part 2-27: Tests — Test Ea and guidance: Shock
IEC 60068-2-42, Environmental testing — Part 2-42: Tests — Test Kc: Sulphur dioxide test for contacts and
connections
IEC 60068-2-75, Environmental testing — Part 2-75 Tests – Test Eh: Hammer tests
IEC 60068-2-78, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
IEC 60529, Degrees of protection provided by enclosures (IP code)
IEC 62262, Degrees of protection provided by enclosures for electrical equipment against external mechanical
impacts (IK code)
IEC 62599-2, Alarm systems — Part 2: Electromagnetic compatibility — Immunity requirements for components
of fire and security alarm systems
3 Terms and definitions
3.1 Definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1.1
controller
information technology equipment as part of thermal image fire detectors that record and/or perform
analytics on images
Note 1 to entry: The controller may be remote from the sensor.
3.1.2
response threshold value
T
temperature at which a detector signals an alarm when tested as specified in 5.1.6
3.1.3
field of view
FOV
image captured by the thermal image fire detector
Note 1 to entry: The FOV can be expressed as an angle or as a width and height, at a specified distance.
3.1.4
thermal image fire detector
TIFD
self-contained device or distributed system in which the analysis of thermal images is performed to measure
temperature in order to detect the likely presence of fire within the images being analysed
3.2 Abbreviated terms
EM electromagnetic compatibility
FDCIE fire detection control and indicating equipment
FOV field of view
MIC measuring ionization chamber
IP ingress protection
RTV response threshold value
TIFD thermal image fire detector
4 Requirements
4.1 Conformity
In order to conform to this document, the TIFD shall meet the following requirements:
a) conform to the requirements of Clause 4, which shall be verified by visual inspection or engineering
assessment;
b) be tested as specified in Clause 5, meeting the requirements of the tests;
c) be marked in accordance with Clause 7 and be accompanied by the documentation specified in Clause 8,
which shall be verified by visual inspection.
4.2 Fire phenomena
The manufacturer shall declare, in the data presented in Clause 8, the stimulus to which the TIFD is
designed to respond. The stimulus that the TIFD responds to shall consist of objects radiating in the infrared
wavelength and optionally, flames.
4.3 Immunity to unwanted alarms
Detectors shall be immune from phenomena that can cause unwanted alarms.
Tests shall be performed where the manufacturer claims immunity to the phenomena.
4.4 Detection range
The manufacturer shall declare the ranges at which the TIFD shall detect a fire in the data supplied in
Clause 8. The manufacturer shall define the size of the hot object which can be detected at the declared
distance.
4.5 Camera lens monitoring
Complete obscuration of the camera lens that inhibits fire detection in the operating FOV shall cause a fault
signal.
4.6 Individual alarm indication
Where the TIFD does not display an image of the FOV to the user, then each thermal image fire detector
shall be provided with an integral red visual indicator by which the individual detector signalling an alarm
can be identified, until the alarm condition is reset. Where other conditions of the detector can be visually
indicated, these shall be clearly distinguishable from the alarm indication.
Where the indicator is mounted on the camera, the visual indicator shall be visible from a distance of 6 m in
an ambient light intensity up to 500 lx at an angle of up to:
a) 5° from the axis of the detector in any direction, and
b) 45° from the axis of the detector in at least one direction.
4.7 Connection of ancillary devices
The detector may provide for connections to ancillary devices (remote indicators, control relays, etc.), but
open- or short-circuit failures of these connections shall not prevent the correct operation of the detector.
4.8 Monitoring of detachable cameras
For detachable cameras, a means shall be provided to detect the disconnection of the camera, in order to
give a fault signal.
4.9 Connection of more than one TIFD to the FDCIE transmission path
Where a TIFD is designed to share the transmission path to the FDCIE with other devices; connections shall
be such that a single transmission fault does not prevent an alarm signal from more than one TIFD.
Where more than one TIFD share the transmission path to the FDCIE, connections shall be such that one
TIFD fault signal does not prevent the alarm signal from any other TIFD.
A TIFD fault shall raise a fault at the FDCIE where the TIFD forms part of a distributed system and
transmission path to the FDCIE connecting other devices.
4.10 Manufacturer's adjustments
It shall not be possible to change the manufacturer's settings, including the response behaviour of the TIFD,
except by special means (e.g. the use of a special code or tool) or by breaking or removing a seal.
4.11 On-site adjustment of response behaviour
If there is provision for on-site adjustment of the response behaviour of the detector, then:
a) for all of the settings at which the manufacturer claims conformance, the detector shall conform to the
requirements of this document and access to the adjustment means shall be possible only by the use of a
code or special tool or by removing the detector from its base or mounting;
b) any setting or settings at which the manufacturer does not claim conformance to this document shall
be accessible only by the use of a special code or tool, and it shall be clearly marked on the detector or
in the associated data that if these setting or settings are used, the detector does not conform to this
document.
Adjustments may be carried out at the TIFD or at the fire detection control and indicating equipment.
4.12 Protection against the ingress of foreign bodies
The manufacturer shall declare, in the data presented in Clause 8, an enclosure protection rating (i.e. IP
rating in accordance with IEC 60529) from Table 1 to which the TIFD is designed to be protected against.
Table 1 — Thermal image fire detector enclosure protection
IP rating (minimum)
Application
(see IEC 60529)
Indoor 30
Outdoor 54
Other A rating nominated by the manufacturer
exceeding the minimum for the application.
Where the TIFD includes more than one subassembly (e.g. a separate sensor and controller), some parts of
the detector not designed to be installed in the environment to which the rating applies need not be assessed.
In this case, the manufacturer's data shall declare the IP rating of each subassembly.
4.13 Operating temperature
The manufacturer shall declare the operating temperature specified in Table 2 to which the TIFD is designed
to operate.
Table 2 — Thermal image fire detector operating environment
Temperature
Application
°C
Indoor controlled 0 to 40
Indoor −10 to 55
Outdoor 1 −25 to 70
Outdoor 2 −40 to 55
Where the TIFD includes more than one subassembly (e.g. a separate sensor and controller i.e. a distributed
system), some parts of the TIFD not designed to be installed in the temperature to which the rating applies
shall be assessed separately for their intended installation location. In this case, the manufacturer's data
shall declare the environment suitable for each subassembly.
NOTE It is acceptable for a manufacturer to declare more than one temperature range. In this case, the testing
would be at the extremes of either range.
4.14 Software
4.14.1 General
The requirements of 4.14.2 and 4.14.3 shall be met for detectors which rely on software control in order to
fulfil the requirements of this document. See 8.2 for information on software data documentation.
4.14.2 Software design
In order to ensure the reliability of the detector, the following requirements for software design apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data
to cause error in the program operation;
c) the software shall be designed to avoid the occurrence of deadlock of the program flow.
4.14.3 Storage of programs and data
4.14.3.1 The program necessary to conform to this document and any preset data, such as manufacturer's
settings, shall be held in non-volatile memory. Writing to areas of memory containing this program and data
shall be possible only by the use of a special tool or code and shall not be possible during normal operation of
the detector.
4.14.3.2 Site-specific data shall be held in memory which will retain data for at least two weeks without
external power to the detector, unless provision is made for the automatic renewal of such data, following
loss of power, within 1
...