FprEN IEC 61643-361:2026
(Main)Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods
Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods
IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating. This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions. [1] Numbers in square brackets refer to the Bibliography.
Bauelemente für den Überspannungsschutz bei Niederspannungen - Teil 361: Überspannungs-Trenntransformatoren (SIT) in Niederspannungsnetzen - Anforderungen und Prüfverfahren
Parafoudres basse tension - Partie 361: Transformateurs d’isolement contre les surtensions (SIT) connectés aux réseaux de distribution basse tension - Exigences et méthodes d’essai
IEC 61643-361: 2026 s’applique aux transformateurs d’isolement contre les surtensions (SIT) destinés à atténuer les surtensions et à être connectés à des circuits d’alimentation 50/60 Hz et à des équipements d’une tension assignée allant jusqu’à 1 000 V en valeur efficace. Le présent document couvre les performances en matière de surtension et d’atténuation des SIT dont la tension de tenue aux chocs atteint au moins 30 kV, et fournit des méthodes normalisées d’essai et d’évaluation. Le présent document couvre les paramètres liés aux surtensions, mais ne traite pas des essais et paramètres types des transformateurs couverts par la série IEC 61558 [13][1]. Le présent document ne couvre pas non plus le fonctionnement d’un SIT dans des conditions de surtension due à la foudre en mode différentiel. [1] Les chiffres entre crochets renvoient à la Bibliographie.
Nizkonapetostni sestavni deli za zaščito pred prenapetostnimi udari - 361. del: Prenapetostni izolacijski transformatorji (SIT) za nizkonapetostne napajalne sisteme - Zahteve in preskusne metode
General Information
- Status
- Not Published
- Publication Date
- 14-Jun-2026
- Current Stage
- 5060 - Voting results sent to TC, SR - Formal Approval
- Start Date
- 13-Mar-2026
- Completion Date
- 13-Mar-2026
Overview
FprEN IEC 61643-361:2026 establishes the requirements and test methods for surge isolation transformers (SITs) used as low-voltage surge protective components. SITs are key elements in protecting electrical and electronic equipment from transient overvoltages introduced by lightning or switching events in low-voltage distribution systems, operating at up to 1,000V rms, 50/60Hz.
This international standard, developed by CLC and IEC/TC 37B, focuses on defining the surge and mitigation performance characteristics of SITs, particularly their impulse withstand voltage and insulation performance. It sets out standardized testing procedures, assessment methods, and service conditions to ensure that SITs deliver reliable protection where it matters most.
Key Topics
Definition and Purpose of SITs
SITs are isolation transformers designed with enhanced insulation and shielding between primary and secondary windings. Their role is to attenuate and isolate transient overvoltages (commonly caused by indirect lightning surges).Insulation and Shielding
SITs employ reinforced insulation materials and an electric screen or shield to decouple high-frequency surge components between windings, achieving greater impulse withstand voltage than ordinary isolating transformers.Test Methods and Performance Requirements
- Impulse Withstand Voltage: SITs must demonstrate at least 30 kV impulse withstand voltage.
- Insulation Resistance: Requires a minimum of 100 MΩ at DC 500 V.
- Power Frequency Withstand Voltage: SITs need to withstand a test voltage (typically ≥10 kV) applied for one minute.
- Standard Test Conditions: Tests are conducted under controlled temperature, humidity, and altitude to ensure uniformity and reliability.
- Waveform and Pass/Fail Criteria: The standard utilizes a 1,2/50 µs lightning impulse for evaluating insulation, with pass/fail determined by waveform consistency within defined tolerances.
Service Conditions
Specifies environmental conditions such as temperature range (-25°C to 40°C), humidity (up to 90%), and altitude (up to 1,000 m) affecting SIT performance.
Applications
Surge isolation transformers designed and tested according to FprEN IEC 61643-361:2026 are critical in:
- Power Distribution Systems: Protecting sensitive equipment in commercial, industrial, and infrastructure environments.
- Lightning Protection Zones: Establishing boundaries within electrical installations to prevent surges from penetrating protected areas.
- Telecommunication and Control Networks: Safeguarding data and signal integrity by mitigating surge propagation.
- Combination with SPDs: SITs are used in tandem with surge protective devices (SPDs) to provide multi-layered defense in low-voltage systems.
Typical end-users include panel builders, facility managers, OEMs of electrical equipment, and installers working on power quality and surge management solutions.
Related Standards
For integrated surge protection design and compliance, reference the following standards:
- IEC 61643-12: Selection and application principles for surge protective devices connected to low-voltage power systems.
- IEC 62305-4: Protection against lightning - Electrical and electronic systems within structures.
- ITU-T K.95 and ITU-T K.126: Surge parameters and component application for isolating transformers in telecommunication environments.
- IEEE PC62.69: Surge parameter standards for isolating transformers in networking devices and equipment.
- IEC/TR 60664-2-1: Insulation coordination guidelines for low-voltage equipment.
Practical Value
Complying with FprEN IEC 61643-361:2026 ensures SITs deliver consistent and reliable surge mitigation performance, verified through robust testing. Adoption of this standard helps manufacturers deliver products recognized for safety and reliability, while system designers and end-users benefit from improved equipment longevity and reduced downtime due to surge events. Following these standardized requirements is vital for achieving resilience in today’s surge-prone electrical environments.
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
FprEN IEC 61643-361:2026 is a draft published by CLC. Its full title is "Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods". This standard covers: IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating. This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions. [1] Numbers in square brackets refer to the Bibliography.
IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating. This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions. [1] Numbers in square brackets refer to the Bibliography.
FprEN IEC 61643-361:2026 is classified under the following ICS (International Classification for Standards) categories: 29.180 - Transformers. Reactors. The ICS classification helps identify the subject area and facilitates finding related standards.
FprEN IEC 61643-361:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN IEC 61643-361:2025
01-julij-2025
Nizkonapetostni sestavni deli za zaščito pred prenapetostnimi udari - 361. del:
Prenapetostni izolacijski transformatorji (SIT) za nizkonapetostne napajalne
sisteme - Zahteve in preskusne metode
Low-voltage surge protective components - Part 361: Surge isolation transformers (SITs)
connected to low-voltage distribution system - Requirements and test methods
Composants de protection contre les surtensions dans les réseaux basse tension -
Partie 361: Transformateurs d’isolement contre les surtensions (SIT) connectés aux
réseaux de distribution basse tension - Exigences et méthodes d’essai
Ta slovenski standard je istoveten z: prEN IEC 61643-361:2025
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
oSIST prEN IEC 61643-361:2025 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
oSIST prEN IEC 61643-361:2025
oSIST prEN IEC 61643-361:2025
37B/252/CDV
COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 61643-361 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2025-06-06 2025-08-29
SUPERSEDES DOCUMENTS:
37B/247/CD, 37B/250/CC
IEC SC 37B : COMPONENTS FOR LOW-VOLTAGE SURGE PROTECTION
SECRETARIAT: SECRETARY:
United States of America Mr David Richmond
OF INTEREST TO THE FOLLOWING COMMITTEES: HORIZONTAL FUNCTION(S):
ASPECTS CONCERNED:
Electromagnetic Compatibility
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.
This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.
Recipients of this document are invited to submit, with their comments, notification of any relevant “In Some
Countries” clauses to be included should this proposal proceed. Recipients are reminded that the CDV stage is
the final stage for submitting ISC clauses. (SEE AC/22/2007 OR NEW GUIDANCE DOC).
TITLE:
Low-voltage surge protective components - Part 361: Surge isolation transformers (SITs)
connected to low-voltage distribution system – Requirements and test methods
PROPOSED STABILITY DATE: 2030
NOTE FROM TC/SC OFFICERS:
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, or any part of it,
for any other purpose without permission in writing from IEC.
oSIST prEN IEC 61643-361:2025
2 IEC CDV 61643-361 ED1 © IEC 2025
1 CONTENTS
3 FOREWORD . 3
4 INTRODUCTION . 5
5 1 Scope . 6
6 2 Normative references . 6
7 3 Terms, definitions and symbols . 6
8 3.1 Terms and definition . 6
9 3.2 Symbols . 8
10 3.3 Abbreviations and acronyms . 8
11 4 Service condition . 9
12 4.1 Temperature range . 9
13 4.2 Humidity range. 9
14 4.3 Altitude and air pressure . 9
15 5 SIT surge condition . 9
16 5.2 SITs surge mitigation . 10
17 6 Electrical requirements . 11
18 6.1 General . 11
19 6.2 Insulation resistance . 11
20 6.3 Power frequency withstand voltage . 11
21 6.4 Impulse withstand voltage . 12
22 7 Type tests . 12
23 7.1 General . 12
24 7.2 Test condition . 12
25 7.3 Sample preparation . 12
26 7.4 Insulation resistance . 12
27 7.5 Power frequency withstand voltage . 13
28 7.6 Impulse withstand voltage . 14
29 Annex A (informative) 1,2/50 impulse . 17
30 Bibliography . 18
32 Figure 1– Symbol of SIT for single phase low-voltage power system . 8
33 Figure 2–Symbol of SIT for single phase low-voltage power system . 8
34 Figure 3 – SITs under common mode surge condition . 11
35 Figure 4 – Sample preparation . 12
36 Figure 5 – Test circuit of insulation resistance . 13
37 Figure 6 – Power frequency withstand voltage test circuit . 14
38 Figure 7 – Construction of pass/fail template from the 1,2/50 open-circuit waveform . 15
39 Figure 8 – Pass/fail template and test waveforms . 15
40 Figure 9 – Impulse withstand voltage test circuit . 16
41 Figure A.1 – 1,2/50 time periods and voltage amplitudes . 17
43 Table 1 – List of abbreviations and acronyms used in this standard . 8
44 Table 2 – Conditions used for test . 12
45 Table A.1 – 1,2/50 voltage impulse generator parameters . 17
oSIST prEN IEC 61643-361:2025
IEC CDV 61643-361 ED1 © IEC 2025 3
47 INTERNATIONAL ELECTROTECHNICAL COMMISSION
48 IEC SC37B JWG5
50 LOW-VOLTAGE SURGE PROTECTIVE COMPONENTS –
52 Part 361: Surge isolation transformers (SITs) connected to low-voltage
53 distribution system – Requirements and test methods
56 FOREWORD
57 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
58 all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
59 co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
60 in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
61 Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
62 preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
63 may participate in this preparatory work. International, governmental and non-governmental organizations liaising
64 with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
65 Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
66 2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
67 consensus of opinion on the relevant subjects since each technical committee has representation from all
68 interested IEC National Committees.
69 3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
70 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
71 Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
72 misinterpretation by any end user.
73 4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
74 transparently to the maximum extent possible in their national and regional publications. Any divergence between
75 any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
76 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
77 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
78 services carried out by independent certification bodies.
79 6) All users should ensure that they have the latest edition of this publication.
80 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
81 members of its technical committees and IEC National Committees for any personal injury, property damage or
82 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
83 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
84 Publications.
85 8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
86 indispensable for the correct application of this publication.
87 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
88 rights. IEC shall not be held responsible for identifying any or all such patent rights.
89 International Standard IEC 61643-361 has been prepared by subcommittee SC37B JWG5, of
90 IEC technical committee TC37
91 This edition includes the following significant technical changes with respect to the previous
92 edition:
93 a) .;
94 b)
95 The text of this International Standard is based on the following documents:
Draft Report on voting
XX/XX/FDIS XX/XX/RVD
97 Full information on the voting for its approval can be found in the report on voting indicated in
98 the above table.
99 The language used for the development of this International Standard is English [change
100 language if necessary].
oSIST prEN IEC 61643-361:2025
4 IEC CDV 61643-361 ED1 © IEC 2025
101 This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
102 accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
103 at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
104 described in greater detail at http://www.iec.ch/standardsdev/publications.
105 The committee has decided that the contents of this document will remain unchanged until the
106 stability date indicated on the IEC website under webstore.iec.ch in the data related to the
107 specific document. At this date, the document will be
108 • reconfirmed,
109 • withdrawn,
110 • replaced by a revised edition, or
111 • amended.
oSIST prEN IEC 61643-361:2025
IEC CDV 61643-361 ED1 © IEC 2025 5
113 INTRODUCTION
114 This standard cover SITs (surge isolation transformers) whose rated impulse withstand
115 voltage coordinates with the expected surge environment of the installation location.
116 This type of surge protective component, SPC, isolates and attenuates transient voltage
117 in conjunction with current diverting components (or SPDs).
118 SITs are a product with specific enhanced insulation layers between the primary and
119 secondary windings and an shield (electric screen) inserted between primary and
120 secondary. With these shields and specific enhanced insulation layers, the surge that
121 appears between the primary winding and earth (common-mode) is greatly attenuated
122 and appears between the secondary winding and earth. SITs are product with a
123 particularly improved impulse withstand voltage compared to ordinary isolating
124 transformers.
125 SITs should be protected by SPDs at their primary side to avoid any damage to the SIT
126 itself. SITs are intended to be used in surge protection to establish lightning protection
127 zones.
oSIST prEN IEC 61643-361:2025
6 IEC CDV 61643-361 ED1 © IEC 2025
129 LOW-VOLTAGE SURGE PROTECTIVE COMPONENTS –
131 Part 361: Surge isolation transformers (SITs) connected to low-voltage
132 distribution system – Requirements and test methods
136 1 Scope
137 This part of IEC 61643 applies to surge isolation transformers (SITs) dedicated to surge
138 mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000V rms.
139 This document covers the surge and mitigation performance of SITs with an impulse withstand
140 voltage performance at least 30 kV, and provides standard methods for testing and rating.
141 This document covers surge-related parameters but does not address typical transformer tests and
142 parameters covered by the IEC 61558 series. This document also does not cover SIT operation under
143 differential mode lightning surge conditions.
144 2 Normative references
145 The following documents are referred to in the text in such a way that some or all of their content
146 constitutes requirements of this document. For dated references, only the edition cited applies.
147 For undated references, the latest edition of the referenced document (including any
148 amendments) applies.
149 IEC/TR 60664-2-1 Ed. 2.0, Insulation coordination for equipment within low-voltage systems -
150 Part 2-1: Application guide - Explanation of the application of the IEC 60664 series,
151 dimensioning examples and dielectric testing
152 IEC 60060-1 Ed. 3.0:2010, High-voltage test techniques - Part 1: General definitions and test
153 requirements
154 IEC 60068-1 Ed. 7.0:2013, Environmental testing - Part 1: General and guidance
156 3 Terms, definitions and symbols
157 3.1 Terms and definition
158 For the purposes of this document, the following terms and definitions apply.
159 ISO and IEC maintain terminological databases for use in standardization at the following
160 addresses:
161 • IEC Electropedia: available at http://www.electropedia.org/
162 • ISO Online browsing platform: available at http://www.iso.org/obp
163 3.1.1
164 surge isolation transformer, SIT
165 isolation transformer which has high impulse withstand voltage with shielding between primary
166 and secondary windings
167 3.1.2
168 electric screen, electric shield (US)
169 screen of conductive material intended to reduce the penetration of an electric field into a given
170 region
171 [SOURCE: IEC 60050-151-13-10]
oSIST prEN IEC 61643-361:2025
IEC CDV 61643-361 ED1 © IEC 2025 7
172 3.1.3
173 clearance
174 shortest distance in air between two conductive parts or between conductive parts and earthed
175 parts
176 [SOURCE: IEC 60664-1:2020, 3.1.4, modified]
177 3.1.4
178 creepage distance
179 shortest distance along the surface of a solid insulating material between two conductive parts
180 [SOURCE: IEC 60050-151:2001, 151-15-50]
181 3.1.5
182 impulse withstand voltage
183 highest peak value of impulse voltage of prescribed form and polarity which does not cause
184 breakdown of insulation under specified condition
185 [SOURCE: IEC 60664-1:2020, 3.1.15]
186 3.1.6
187 electric insulation
188 Part of an electrotechnical product which separates the conducting parts at different electrical
189 potentials during operation or insulates such parts from the surroundings
190 [SOURCE: IEC 60664-1:2020, 3.1.28]
191 3.1.7
192 insulation resistance
193 resistance under specified condition between two conductive elements separated by insulation
194 materials
195 [SOURCE: IEC 60050-151-15-43]
196 3.1.8
197 power frequency withstand voltage
198 rms value of sinusoidal power frequency voltage that the insulation of the given equipment can
199 withstand during tests made under specified conditions and for a specified duration
200 [SOURCE: IEC 60050-614-03-22]
201 3.1.9
202 electric breakdown
203 failure of insulation under electric stress when the discharge completely bridges the insulation,
204 thus reducing the voltage between the electrodes almost to zero
205 [SOURCE: IEC 60664-1:2020, 3.1.44]
206 3.1.10
207 virtual f
...




Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...